c. Tighten locking band by HAND with a 5/16”

nut driver until snug plus ¼ turn. DO NOT

SECURE JOINTS WITH SHEET METAL

SCREWS OR POP RIVETS. DO NOT

PUNCTURE THE VENT SYSTEM!

d. Once the installation is complete, operate

appliance and inspect all joints to ensure that flue

gases and/or liquid condensate will not escape.

D.

Horizontal Venting System.

See Figures 4, 4A and 5.

Vent Piping

1. This boiler is supplied with components as standard

equipment for installation of the separate horizontal

venting system.

2. Do not exceed maximum vent lengths. Refer to

Table 4.

3. Recommended horizontal installation consists of

vent being sloped down ¼ inch per foot away from

boiler. See Figures 4 and 4A.

4. Use appropriate designed thimbles when passing

through combustible walls (thimble use optional for

noncombustible walls). Insert thimble through wall

from outside. Secure outside flange to wall with

nails or screws, and seal ID, OD and vent holes with

sealant material. Install inside flange to inside wall,

secure with nails or screws, and seal with sealant

material.

5. For noncombustible wall application when thimble

is not used, size opening such that bell with locking

band attached cannot pass through.

6. Join vent terminal to vent pipe. See Figure 5.
7. Insert vent pipe through thimble/opening from

outside and join to vent system. Apply sealant

between vent pipe and opening/thimble to provide

weathertight seal.