Bryant 702B User Manual
Page 20

—20—
702B WITH ICM FIOP ELECTRICAL DATA
ELECTRICAL DATA LEGEND
UNIT
SIZE
702B
V-PH-Hz
VOLTAGE
RANGE
COMPRESSOR
OUTDOOR
FAN MOTOR
INDOOR
FAN MOTOR
ELECTRIC HEAT
SINGLE POINT
POWER SUPPLY
Min
Max
RLA
LRA
FLA
FLA
Nominal kw*
FLA
UNIT MCA
MAX FUSE
or CKT. BKR.
MOCP
024
208/230-1-60
187
253
13.5
61.0
0.8
4.3
—/—
3.8/5.0
5.4/7.2
7.5/10.0
—/—
18.1/20.8
25.9/30.0
36.1/41.7
22.2/22.0
27.9/31.4
37.8/42.9
50.5/27.5
30/30
30/35
40/50
60/60
—
—
—
—
030
208/230-1-60
187
253
14.7
73.0
0.8
4.3
—/—
3.8/5.0
5.4/7.2
7.5/10.0
—/—
18.1/20.8
25.9/30.0
36.1/41.7
23.5/23.5
27.9/31.4
37.8/42.9
50.5/57.5
30/30
30/35
40/50
60/60
—
—
—
—
036
208/230-1-60
187
253
16.9
83.0
1.6
6.8
—/—
3.8/5.0
5.4/7.2
7.5/10.0
11.3/15.0
—/—
18.1/20.8
25.9/30.0
36.1/41.7
54.2/62.5
26.9/26.9
31.1/34.5
40/9/46.0
53.6/60.6
76.2/86.6
35/35
35/40
50/50
60/–
—
—
—
—
–/70
80/90
042
208/230-1-60
187
253
22.4
105.0
0.9
6.8
—/—
3.8/5.0
5.4/7.2
7.5/10.0
11.3/15.0
15.0/20.0
—/—
18.1/20.8
25.9/30.0
36.1/41.7
54.2/62.5
72.2/83.3
30.9/30.9
31.1/34.5
40.9/46.0
53.6/60.6
76.2/86.6
98.8/112.7
40/10
40/40
50/50
60/–
—
—
—
—
—
–/70
90/90
100/125
048
208/230-1-60
187
253
20.5
109.0
1.6
6.8
—/—
3.8/5.0
5.4/7.2
7.5/10.0
11.3/15.0
15.0/20.0
—/—
18.1/20.8
25.9/30.0
36.1/41.7
54.2/62.5
72.2/83.3
34.0/34.0
34.0/34.5
40.9/46.0
53.6/60.6
76.2/86.6
98.8/112.7
40/40
40/40
50/50
60/–
—
—
—
—
—
–/70
90/90
100/125
060
208/230-1-60
187
253
27.6
158.0
1.6
9.1
—/—
3.8/5.0
5.4/7.2
7.5/10.0
11.3/15.0
15.0/20.0
—/—
18.1/20.8
25.9/30.0
36.1/41.7
54.2/62.5
72.2/83.3
45.2/45.2
45.2/45.2
43.8/48.9
56.5/63.5
79.1/89.5
101.6/115.5
60/60
60/60
50/50
60/–
—
—
—
—
—
–/70
90/90
110/125
452 = 5 v
457 = 7 v
455 = 2 v
LEGEND
FLA
— Full Load Amps
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
RLA
— Rated Load Amps
NOTES:
1. In compliance with NEC (National Electrical Code) requirements
for multimotor and combination load equipment (refer to NEC
Articles 430 and 440), the overcurrent protective device for the
unit shall be Power Supply fuse . The CGA (Canadian Gas
Association) units may be fuse or circuit breaker.
2. Minimum wire size is based on 60 C copper wire. If other than
60 C wire is used, or if length exceeds wire length in table,
determine size from NEC.
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%. Use the following formula to determine
the percentage of voltage imbalance.
% Voltage imbalance
max voltage deviation from average voltage
= 100 x
average voltage
EXAMPLE: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
452 + 464 + 455
Average Voltage =
3
1371
=
3
= 457
Determine maximum deviation from average voltage.
(AB) 457
(BC) 464
(AC) 457
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
7
% Voltage Imbalance = 100 x
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately.
®
*Heater capacity (KW) based on heater voltage of 208v, 240v, & 480v.
If power distribution voltage to unit varies from rated heater voltage,
heater KW will vary accordingly.