10 Application example: DI30 and gas cylinder scale GCS-1

WIKA operating instructions digital indicator model DI30

37

Adjustment
With the program numbers 0, 1, 2 and 3 the indicator is configured according
to the connected scale.
For program number 5 „Offset shift on display value“ the TARA-value has to
be entered as negative value. The weight of the scale is subtracted
automatically, only the actual weight of the filling will be shown in the display.

PN Function

Set values

0

Input signal

2 = 4 ... 20 mA

1

Scaling final value
(value, which is shown at 20 mA;
Corresponds to the full measuring range of
GCS-1)

1361

2

Scaling starting value
(value which is shown at 4 mA;
Corresponds to the beginning of the measuring
range)

0

3

Number of decimal places after separator

1 = 0,0

5

Offset shift on display value
(negative TARA value, which is printed on the
gas cylinder)

-20,0


If an alarm should be activated at an certain filling level (eg. 5 kg) the alarm
output (eg. A1) has to be configured accordingly:

Alarm output 1
60

Alarm output 1

1 = activated

61

Threshold

5


Program numbers P62…P65 have to be set accordingly to your technical
conditions.