PN
Function
Range of value
De-
fault
User
level
Alarm output 1
60
Alarm output 1
0 = deactivated
1 = activated
1
4
61
Threshold
-999 ... 9999
1000
6
62
Hysteresis
1 ... 9999
1
5
63
Active below / above
threshold value
0 = active below
1 = active above
1
4
64
Switch delay
0 … 1000 seconds
1
4
65
Delay type
0 = none
1 = switch-on delay
2 = switch-off delay
3 = switch-on/-off delay
0
4
Alarm output 2
70
Alarm output 2
0 = deactivated
1 = activated
1
4
71
Threshold
-999 ... 9999
1000
6
72
Hysteresis
1 ... 9999
1
5
73
Active below / above
threshold value
0 = active below
1 = active above
1
4
74
Switch delay
0 … 1000 seconds
1
4
75
Delay type
0 = none
1 = switch-on delay
2 = switch-off delay
3 = switch-on/-off delay
0
4
Linearisation
100
Number of additional
setpoints
0 ... 10
0
2
101...
110
Setpoints 1 ... 10
-999 ... 9999
2
Information
200
Serial number
0 ... 9999
0
8