beautypg.com

Instruction manual ni-223e – WIKA DE User Manual

Page 3

background image

INSTRUCTION MANUAL

NI-223E

Rev. 2 11/02



Fig. 2 -

Electrical connections and adjustament screws with one or two contacts instruments

1 - Adjustment screw
2 - Screw for fixing the adjustement
3 - Terminal block for the first microswitch
4 - Hole for test plug
5 - Terminal block for the first microswitch
6 - Internal earth screw
7 - Pre-insulated thimbles
8 - External earth screw
9 - Adjustment bush access plate

10 - Graduated dial

Microswitch electrical circuit.
State of the contacts at atmospheric pressure

Designation of the contacts:
C – Common
NA – Normaly open
NC – Normaly closed

5 - SET POINT CALIBRATION

In order to proceed with the calibration and the periodical func-
tional verification of the instrument a suitable calibration circuit
(fig.4) and an adequate pressure source is required.

5.1 PRELIMINARY OPERATIONS

CAUTION: do not open the cover of explosionproof pressure
switches (Series DE) when energized, in explosive atmospheres.

With reference to fig.3 unscrew the screw (b) until the blocking
device (a) can be turned 180°; then unscrew the cover.

Fig. 3 -

Cover blocking device and plumbing

a - Cover blocking device
b - Blocking screw
c - Screw blocking the adjustment bush access plate
d - Flexible steel wire
e - Plumbing
f - Adjustment bush access plate

5.2 CALIBRATION CIRCUIT AND OPERATIONS

Prepare the control circuit as indicated in Fig. 3 by connecting the
+ (or H) port to the pressure source and leaving the - (or L) port
open to the atmosphere.
The warning lamps should be connected to the contacts in the
NA or NC (NA = Normally Open NC = Normally Closed) position
according to the required contact action.

If the instrument is equipped with two microswitches, take into
account that they actuate simultaneously within rated tolerances.

The warning lamps can either be connected by means of a thim-
ble with a maximum diameter of 2.5 mm or by means of a test

plug with a diameter of 2 mm to be inserted in the appropriate
holes situated frontally beside the terminal screw (see fig.2).
Connection of C and NO terminals
If the circuit is open at the working pressure, the switch closes
the circuit as the pressure increases when the desired values is
reached (MAKE on Raise).
If the circuit is closed at the working pressure, the switch opens
the circuit as the pressure decreases when the desired value is
reached (BREAK on Fall).
Connection of C and NC terminals
If the circuit is closed at the working pressure, the switch opens
the circuit as the pressure increases when the desired value is
reached (BREAK on Raise).
If the circuit is open at the working pressure, the switch closes
the circuit as the pressure decreases when the desired value is
reached (MAKE on Fall).
The test instrument should have a measurement range approxi-
mately equal to or slightly wider than the differential pressure
switch range and should have an accuracy consistent with the
precision required to calibrate the set point.
The differential pressure switch must be mounted in the normal
installation position, i.e. with the pressure connections down-
wards.

Fig. 4 -

Calibration circuit

DPS Differential pressure switches

Test fluid:

CA

Test gauge

air for

P

≤ 10 bar

V1

Inlet valve

water for P > 10 bar

V2 Discharge

valve

P Pressure

source

Avoid forcing the microswitch by hand or with tools. This could af-
fect the instrument functioning.
With reference to fig.3, clear the access to the adjustment bush
by loosening the screw (c) which holds the access plate (f).

5% span

This manual is related to the following products: