WIKA Operating instructions pressure gauges Model 6 with 831 per ATEX

2030660 12/2004 GB/D/F

GB

The permissible limits for U

i

, I

i

and P

i

of the intrinsically safe supply circuits

depend on the sensor type. They can be taken from the corresponding EC-type

examination certificates. (The sensor type is stated on the connection plate of

the pressure gauge.)

Suitable switch amplifiers are e.g.:

4. Alarm contacts

Circuit

Sensor type Model designation

EC-type exami-

WIKA-

(s. Ex-certific.)

Fa. Pepperl & Fuchs

nation certificate

Model

Model 1

standard

KFD2-SR2-Ex1

PTB 00 ATEX 2080

904.31

standard

KFD2-SR2 Ex2

PTB 00 ATEX 2080

904.32

Model 2

standard

KFA6-SR2-Ex1

PTB 00 ATEX 2081

904.28

standard

KFA6-SR2-Ex2

PTB 00 ATEX 2081

904.29

SN-sensors

KFD2-SH-Ex1

PTB 00 ATEX 2042

904.33

SN-sensors

KHA6-SH-Ex1

PTB 00 ATEX 2043

904.30

The desired value indicators for the alarm contacts are adjustable over the full

range of the instrument. Switching points shall be set in the ranges between

10 % und 90 % of the scale, to ensure switching accuracy and long life of the

mechanical measuring system.

Adjustment key
removable

Desired value

indicators

(red set pointer)

Adjustment lock

Electromagnetic compatibility
EMC according to EN 60 947-5-2.

The instruments are to be protected against strong electromagnetic fields.

To set desired value indicator
The desired value indicators for the alarm contacts are adjustable over the

adjustment lock in the window with the aid of adjustment key (included in deli-

very; to be found on standard gauges on the outside edge of the junction box).