Specifications – WIKA 890.09.2190 User Manual

Page 7

background image

WIKA operating instructions differential pressure transmitter model 890.09.2190

7

GB

11171545.02 08/2010 GB/D/F/E

3. Specifications

General

Process connection

2 x 7/16 UNF male thread

Materials

„

Pressure connections

„

Sealings

„

Media chamber

„

Sensor element

Cu alloy - wetted

FPM/FKM - wetted

Zinc diecast - wetted

Ceramic Al

2

O

3

- wetted

Differential pressure measuring

ranges

0 ... 1 bar, 0 ... 2 bar, 0 ... 4 bar, 0 ... 6 bar or

0 ... 10 bar

Max. working pressure (stat.)

21 bar

Overpressure safe either side

max.

2.5 x end value of measuring range, max. 21 bar

Pressure spikes are to be reduced through

constructive measures (e.g. capillaries)

Measurement time constant

T

mess

= 10 ms (sensor + electronics)

Accuracy (error band)

± 2 % of span (linearity, hysteresis, temperature

error 10 ... 70 °C)

Linearity, hysteresis

± 1 % of span

Temperature coefficient

0.2 % of span / 10 K

Zero offset

± 0.1 mA

Permissible ambient temperature -10 °C ... 50 °C

Permissible medium temperature -10 °C … 80 °C

Ingress protection

IP 55 per EN 60529 / IEC 529

Electrical data

Nominal voltage

DC 24 V

Permissible supply voltage

DC 18 … 30 V

Electrical connection

3-wire

Output signal

4 ... 20 mA

Max. load

500 Ohm

Current supply

„

at output max.

„

at current limitation

approx. 32 mA normal (typical)

approx. 36 mA (at overpressure)

Wiring protection

Short-circuit-proof, after eliminating the fault the

operability is recovered

Electrical connection

„

3-wire numbered cable

„

Connection with snap-in M8

connector (3-pin)

0.34 mm², 0.8 m to 2.5 m long

replaceable at the instrument, outer cable end

with single wires for clamping

3. Specifications