1
Outdoor Discharge over temperature error
Indoor display
ሱ
ل
ሱ
Outdoor error
Outdoor display
ሱ
ƻ
م
Outdoor
Discharge
over
temperature
error
1.Checklist :
1) Check the discharge temperature in the outdoor unit
2) Check the compressor locking or gas leak
3) Download the EEPROM data
2. Troubleshooting procedure
Is the discharge over temperature
sensor error appeared again?
Terminate the service
NO
a
Ōer 30min ~ 1Hr
YES
Is the discharge over temperature
sensor error appeared again?
The condi
Ɵon is too poor for air condiƟoner to
operate
Wait un
Ɵl discharge temperature is decreased
Restart a
Ōer power oī
YES
Download the EEPROM data
Is the discharge over temperature
sensor error appeared again?
YES
Terminate the service
Terminate the service
NO
NO
Exchange the Outdoor PBA
Exchanged the Compressor
Restart a
Ōer power oī.