beautypg.com

2-15 dc link over voltage/ low voltage error, 2-16 the others – Sunlight Supply Samsung Programmable Thermostat for Split Systems User Manual

Page 111

background image

Samsung Electronics 12-48

12-2-15 DC

Link Over voltage/ Low voltage error

1. Checklist

:

1) Is the power voltage normal?(Lightning, Power interruption etc.)

2) Is AC Power cable connection normal?(Detaching the wire)

2.

Troubleshooting

procedure

Yes

No

No

No

No

Yes

Yes

Yes

Push the center bar of M/C and mesure the resis-

tance of each contact.

Yes

No

Exchange M/C

Check and reconnecting the

AC power cable wire

Is the AC Power cable connection to the outdoor

unit terminal block good?

Check and reconnecting the reactor wire

at the TAB terminal

Is the connection of reactor terminal good?

Replace the blown FUSE

Are the FUSEs on EMI PCB blown?

Is each contact resistance normal?

(less than 0.1ohm)

Does the error reappear frequently

The cause of this error may be power source

trouble as like power interruption.

Check the power source.

Exchange INVERTER PCB

12-2-16 The others

1. Capacity miss match

– Check again the indoor unit option code.

This manual is related to the following products: