Comfort-Aire HCG**V1E Series User Manual
Page 21

21
HCG24V1E & HCG30V1E
CFM
SWITCH SETTINGS
(1 = ON, 0 = OFF)
NOMINAL
CAPACITY
5
6
7
8
525
0
0
0
0
1.5 T
ON
560
0
0
0
1
600
0
0
1
0
625
0
0
1
1
700
0
1
0
0
2 T
ON
750
0
1
0
1
800
0
1
1
0
2.5 T
ON
850
0
1
1
1
875
1
0
0
0
890
1
0
0
1
930
1
0
1
0
950
1
0
1
1
1000
1
1
0
0
3 T
ON
1050
1
1
0
1
1125
1
1
1
0
1200
1
1
1
1
HCG36V1E & HCG42V1E
HCG48V1E & HCG60V1E
CFM
SWITCH SETTINGS
(1 = ON, 0 = OFF)
NOMINAL
CAPACITY
CFM
SWITCH SETTINGS
(1 = ON, 0 = OFF)
NOMICAL
CAPACITY
5
6
7
8
5
6
7
8
525
0
0
0
0
1.5 T
ON
1100
0
0
0
0
3 T
ON
560
0
0
0
1
1200
0
0
0
1
3.5 T
ON
600
0
0
1
0
1250
0
0
1
0
650
0
0
1
1
2 T
ON
1300
0
0
1
1
4 T
ON
700
0
1
0
0
1350
0
1
0
0
750
0
1
0
1
1400
0
1
0
1
800
0
1
1
0
2.5 T
ON
1450
0
1
1
0
850
0
1
1
1
1500
0
1
1
1
875
1
0
0
0
1550
1
0
0
0
950
1
0
0
1
1600
1
0
0
1
5 T
ON
1050
1
0
1
0
3 T
ON
1650
1
0
1
0
1150
1
0
1
1
3.5 T
ON
1700
1
0
1
1
1250
1
1
0
0
1750
1
1
0
0
1350
1
1
0
1
4 T
ON
1800
1
1
0
1
1400
1
1
1
0
1900
1
1
1
0
1600
1
1
1
1
2000
1
1
1
1
Table 8. Recommended Cooling Airflow Settings for HCG**V1E Air Handlers
FURNACE MODELS
Nominal Electic Heat KW
5
8
10
15
20
25
30
HMG24X1E & HMG30X1E
800
900
1000
1300
N/A
N/A
N/A
HMG36X1E & HMG42X1E
900
1000
1100
1300
1500
N/A
N/A
HMG48X1E & HMG60X1E
1000
1100
1200
1400
1600
1800
2000
NOTE: See Table 6 for appropriate switch settings for these airflows.
Table 7. Minimum Heating Airflow Settings (in CFM)
for HMG**X1E Air Handlers