Caution – Comfort-Aire HCG**V1E Series User Manual

Page 12

background image

12

CAUTION:

Isolation must be maintained from the external

Class 2 output of any transformer in a cooling

circuit. Use a thermostat with isolating contacts

to prevent inter-connection of Class 2 outputs.

• The thermostat should be mounted about 5 feet above

the floor on an inside wall. DO NOT install the thermostat

on an outside wall or any other location where its

operation may be adversely affected by radiant heat from

fireplaces, sunlight, or lighting fixtures, and convective

heat from warm air registers or electrical appliances.

Refer to the thermostat manufacturer’s instruction sheet

for detailed mounting and installation information.

• Install the grommet, which is packed with the unit, in

the hole for low-voltage wires. Properly connect the

low-voltage wiring between the thermostat, outdoor

unit, and control board.

NOTE: When the low voltage

wires are positioned in this grommet, the grommet will

prevent chafing and/or shorting of the low voltage leads.

Control Board
The control board in the air handler controls the timing
sequence of the elements. The board is equipped with a 3
second blower on delay and a 15 second blower off delay
in heating and a 40 second blower off delay in cooling.
See Figures 14 or 15 (page 23) and Table 12 (pages 29-
31) for control board modes and actions.

Twinning
HMG**F1E series air handler’s are not supplied with a
built in twinning capability. To connect two air handlers to a
common single stage AC condensing unit or heat pump, a
twinning kit is available for field installation.

Please follow

the instructions supplied with the kit.

Figure 10. Typical Thermostat Connections

G R C W/E

O Y

Thermostat

G R

W

Thermostat

Y

C

Y

G R

W

Thermostat

Y

C

Air

Handler

Air

Conditioner

Y

Typical Air Conditioner with

Standard Air Handler

G R C E

O Y

Thermostat

Typical Heat Pump with

Standard Air Handler

Typical Air Conditioner with

2-Stage Air Handler

Typical Heat Pump with

2-Stage Air Handler

G R

W2

C

O

Y1

Thermostat

O

Y1

R

C

G R

W/E

Thermostat

Y1

C

Y1

W2

Typical 2-Stage Air Conditioner

with 2-Stage Air Handler

Typical 2-Stage Heat Pump with

2-Stage Air Handler

Y2

Y2

Y2

Y2 OUT

W/E

R

Air

Conditioner

Air

Handler

Air

Conditioner

Air

Handler

Heat Pump

Air

Handler

Heat Pump

O

R

C

Y

Air

Handler

Heat Pump

NOTE: Jumper between
W2 & E is required when
no OD T-Stat is used.

W1

Y

G

R

C

NOTE: Jumper W1 & W2

together if not using W2

on thermostat

Y1

W2

W1

O

Y/Y2

G

R

C

Y1

W2

W1

O

Y/Y2

G

R

C

W2

Air

Handler

W1

Y

G

R

C

R

C

Y

W2

O

Y1

W2

W1

O

Y/Y2

G

R

C

Y1

W2

W1

O

Y/Y2

G

R

C

W2

W2

W2

NOTE: Jumper W1 & W2

together if not using W2

on thermostat