* Status LED Window Description

4. STATUS LED

Item

LED is

State

To indicate :

MOD :

Module

Status LED

Off

No Power

No power is supplied to the unit.

Green

Device Operational

The unit is operating in normal condition.

Blinking

Green

Device in Standby

The EEPROM parameter is not initialized yet.
Serial Number is zero value (0x00000000)

Flashing

Green

IAP Mode

Available for firmware download using FireFox.

Blinking

Red

Minor Fault

The unit has occurred hardware fault in self-testing.

- Memory error

Red

Major Fault

The unit has occurred hardware fault in self-testing.

- CPU error

NET :

Network

Status LED

Not Used

RUN :

Run/Stop

Status LED

OFF

Not Programmed

Not Power is supplied or the unit or Not programmed

ON

Run

PLC Run

Blinking

Green

Stop

PLC Stop

Blinking

Red

Diagnostic

Diagnostic mode

Field Power

LED

Off

Not Supplied Field Power

Not supplied 24V dc field power

Green

Supplied Field Power

Supplied 24V dc field power

I/O :

Expansion

Module

Status LED

Off

Not Powered
No IO Module

Device has no IO module or may not be powered

Flashing

Green

FnBus On-line,
Do not Exchanging I/O

FnBus is normal but does not exchanging I/O data
(Passed the IO module configuration).

Green

FnBus Connection,
Run Exchanging IO

Exchanging I/O data

Red

FnBus connection fault
during exchanging IO

One or more IO module occurred in fault state.
- Changed IO module configuration.
- FnBus communication failure.

Flashing

Red

Expansion Configuration
Failed

Failed to initialize IO module
- Detected invalid IO module ID.
- Overflowed Input / Output Size
- Too many IO module
- Initial protocol failure

* Indicator states and flash rates

Blinking

Flashing