Fnio s-series, Na-9379, Quick guide – Beijer Electronics NA-9379 User Manual
Page 5: Fieldbus input/output system

FieldBus Input/Output System
■ MODBUS Programmable I/O
■ PROFIBUS Network Adapter
■ Digital Input / Output
■ Analog Input / Output
■ Special Module
Quick Guide
FnIO S-series
1. NA-9379 Specification
Class 2, adjacent to voltage rating (30Vmax.)
ITEM
SPECIFICATION
ITEM
SPECIFICATION
Operating/Storage Temp.
-20℃~60℃ / -40℃~85℃
Network Type
Modbus/TCP
Relative Humidity
5% ~ 90% Non-Condensing
Cable
Ethernet Cable(Shield Cable)
Durable-vib./impact
IEC68-2-6(2G) / 10G
Cable Length(m)
Up to 100m from Ethernet Hub
EMC/ESD
EN 61000-6-2:2005
EN 61000-6-4/A11:2011
Max. In/Output Size
/Comm. Sp(Kbps)
126Words / 126Words
10/100Mbps
Mount Position
On the left of FnIO-S series
Expansion No.
Max. 32 Modules
Atmosphere
Not so dusty without corrosive gas Interface Connector
RJ-45 Socket 2pcs
Field Supp. Volt.
Class 2, 24VDC
24VDC (11VDC ~ 28.8VDC)
Programming
/
Program Languages
CoDeSys V3.5 SP3 Patch 1
/IEC 61131-3 (LD, IL, ST, FBD, SFC)
Field Supp. Cur.
Max. 10A
Program Memory
512Kbytes
FnBus Sup. Cur
Max. 1.5A@5Vdc
Data Memory
512Kbytes
Isolation
System power to internal logic :
Non-isolation
System power to I/O driver :
Isolation
Non-Volatile
Memory
32Kbytes
(Retain : 16Kbytes, Flag : 16Kbytes)
Size
54mm × 99mm × 70mm
Max. nodes
Limited by Ethernet Specification
Protocol
MODBUS/TCP, DHCP
BOOTP, SNMP
Configuration
Port(RS232/485)
Node: 1 / Baud rate: 38400 / Data bit: 8
/Parity bit: No parity / Stop bit: 1
Weight
167g
Certification
UL/CE
Cautions for your Safety
Do not assemble the products and wire with power applied to the system. Else it may cause an electric arc, which can result into unexpected
and potentially dangerous action by field devices. Arching is explosion risk in hazardous locations. Be sure that the area is non-hazardous or
remove system power appropriately before assembling or wiring the modules.
Do not touch any terminal blocks or IO modules when system is running. Else it may cause the unit to an electric shock or malfunction.
Keep away from the strange metallic materials not related to the unit and wiring works should be controlled by the electric expert engineer.
Else it may cause the unit to a fire, electric shock or malfunction.
If you don’t follow the directions, it could cause a personal injury, damage to the equipment or explosion
If you disobey the instructions, there may be possibility of personal injury, damage to equipment or
explosion. Please follow below Instructions.
Check the rated voltage and terminal array before wiring. Avoid the circumstances over 60℃ of temperature. Avoid placing it directly in the
sunlight.
Avoid the place under circumstances over 90% of humidity.
Do not place Modules near by the inflammable material. Else it may cause a fire.
Do not permit any vibration approaching it directly.
Go through module specification carefully, ensure inputs, output connections are made with the specifications. Use standard cables for wiring.
Use Product under pollution degree 2 environment.
Before using the unit
*We appreciate you for purchasing CREVIS Products. To use the units more effectively, please read this quick guide and refer to
the respective user manual for further details.
Warning!
Caution!
* Power Isolators must be used according to the usage of 5VDC/24VDC/48VDC or AC Voltage modules
NA-9379
Rev 1.00
Update date : 2014.06.13
Programmable I/O