In absence of local codes, install the appliance to the current National Fuel Gas Code, ANSI Z223.1
Installation Code which can be obtained from:
American National Standards Institute Inc. or

National Fire Protection Association Inc.

1430

Broadway

Batterymarch

Park

New York, NY 10018

Quincy, MA 02269

The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during
any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa). The appliance must be
isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure
testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa). When
installed with a blower the junction box must be electrically connected and grounded in accordance with local
codes. In the absence of local codes, use the current ANSI / NFPA 70 National Electric Code. In the case
where the blower is equipped with a power cord it must be connected into a properly grounded receptacle.
The grounding prong must not be removed from the cord plug.

As long as the required clearance to combustibles is maintained,
the most desirable and benefi cial location for the appliance is in
the center of a building, thereby allowing the most effi cient use of
the heat created. The location of windows, doors and the traffi c
fl ow in the room where the appliance is to be located should be
considered.

If the appliance is installed directly on carpeting, vinyl tile or other
combustible material other than wood fl ooring, the appliance shall be installed on a metal or wood panel
extending the full width and depth. NOTE: This does not apply to stoves.

* Air shortage caused by an inadequate air supply, improper log positions, the addition of foreign or
unapproved materials or the failure to properly maintain the appliance, may result in incomplete combustion of
the fuel. Incomplete combustion results in soot being deposited inside the fi rebox as well as surfaces outside
the appliance. If any soot deposits are observed, shut off the appliance immediately and arrange for it to be
serviced by a qualifi ed technician.

We suggest that our gas
hearth products be installed
and serviced by professionals
who are certified in the U.S.
by the National Fireplace
Institute

® (NFI) as NFI Gas

Specialists

www.nficertified.org

FOR YOUR SATISFACTION, THIS APPLIANCE HAS BEEN TEST-FIRED TO ASSURE ITS OPERATION AND
QUALITY!

GVFS20

NG

LP

Altitude (FT)

0-2,000

0-2,000

Max. Input (BTU/HR)

23,000

23,000

Min. Inlet Gas Supply Pressure

4.5" Water Column

11" Water Column

Max. Inlet Gas Supply Pressure

7" Water Column

13" Water Column

Manifold Pressure (Under Flow Conditions)

3.5" Water Column

10" Water Column

2.3 GENERAL

INFORMATION

When the appliance is installed at elevations above 2,000ft, and in the absence of specifi c recommendations from
the local authority having jurisdiction, the certifi ed high altitude input rating shall be reduced at the rate of 4% for each
additional 1,000ft. Expansion / contraction noises during heating up and cooling down cycles are normal and to be
expected.

No external electricity (110 volts or 24volts) is required for the gas system operation.

This appliance is equipped with a pilot light safety system referred to as an oxygen depletion sensor and is designed to
turn off the appliance if not enough fresh air is available.