8.5 Reduced output

Possible causes

8.6 CH does not reach the correct temperature

8.7

No hot water (HW)

1. Tap flow < 2.0 l/min.

2. Replace the flow switch.

Flow switch does not switch.

1. Replace S3.

See burner does not ignite.

Burner does not ignite.

Yes

Burner does not come in on HW: S3 defect.

Yes

No

No

Yes

1. Check the wiring according to the

diagram.

No voltage on the flow switch (24 V).

Yes

No

Possible causes

Remedies

1. Check the setting and adjust if

necessary: set to 0.1 A.

Room thermostat settings not correct.

1. Raise the pump setting or replace

the pump.

1. Check for circulation: at least 2 or 3

radiators must be open.

1. Adjust the power,

see Setting maximum CH power.

1. Descale or flush the heat exchanger

on the CH side.

No heat transfer due to scaling or pollution

in the heat exchanger.

Yes

The boiler power is not set well

for the system.

Yes

No

No

No circulation in the system.

Yes

Pump does not run well.

Pump setting too low.

Yes

No

No

Yes

1. Raise the CH temperature,

see CH operation.

2. Check the outside sensor for

short circuit: remedy this..

Temperature set too low.

Yes

No

Possible causes

Remedies

1. Check appliance and flue system

At high speed, the power has decreased

Yes

by not more than 5%.

for pollution.

2. Clean appliance and flue system.

Remedies