10 sequence of operation – Aquacal H 100 User Manual

Page 34

background image

10

Sequence of Operation

PUMP OFF

POWER ON

______________________

"FLO" Displayed

PUMP ON

POWER ON

______________________

Water Temp. Displayed

SET POINT BELOW 60ºF

______________________

Heater is "OFF"

Pressing Up-Down

Keys Will Display "OFF",

Water Temp. Displayed

SET POINT ABOVE 60ºF

______________________

Heater in Standby, Waiting

Call for heat

Water Temp. Displayed

CALL for HEAT

______________________

Occurs at Set point + Dead

Band Setting...

Fan Starts

4-MINUTE TIME DELAY

______________________

Compressor Remains Idle,

while Fan Continues to

Operate

COMPRESSOR STARTS

______________________

Compressor & Fan Operate

Until Water Temp. Reaches

Set Point...HEAT LED Lit

(OR UNTIL FAULT OR DEFROST)

HEATING SATISFIED

______________________

Heater Shuts Off when

Water Set Point Reached

20-Second HP Delay

VERSION .07 & UP

_____________________

High Pressure Signals will

be Ignored for 20-Seconds

5-HPs in 1-Hour

VERSION .07 & UP

_____________________

Controller will Lock Out

Heater if more than 5 HP

Signals are Received in

any 1-Hour period

Other Possible Displays

OPERATIONAL CODES

______________________

"FS"...Defrost Mode

Normal Operation in Colder

Weather

FAILURE CODES

______________________

CSE- Control System Error

dPC-Defrost Sensor Shorted

dPO- Defrost Sensor Open

PC- Water Sensor Shorted

PO- Water Sensor Open

LP- Refrigerant Low Pressure

HP5- 5 High Press. Trips < 1Hr

HEATER OFF on CODE

(SEE ABOVE)

Heater will Remain Idle Until

Defrost is Satisfied, or Until

Faults are Cleared

Other Possible Displays

LINK to Codes

LINK to Codes

START

NOTE

VERSION .04 & BELOW

Fan will continue to operate

indefinitely if water temp.

raises into dead band before

compressor starts.

HP-7 (6200P) Sequence of Operation

RETURN to TOP of

PAGE

M. Mauro, 10/14/03

M. Mauro, 10/14/03