APC 3000VA User Manual
Page 7
5
5. Connect the battery and attach the front bezel.
6. Connect the equipment and power to the UPS.
7. Turn on the UPS.
I
NSTALLING THE
M
OUNTING
R
AILS IN THE
R
ACK
Install the mounting rails in the rack. Directions are included with the rail kit. The UPS comes with
standard 19-inch (46.5 cm) rack mounting rails, brackets, and cleats. The rack can have any of the
common types of equipment mounting holes (square, round-threaded, or round-non-threaded). All
necessary hardware is provided.
R
EMOVING THE
B
ATTERY
M
ODULE
The UPS is heavy. To lighten it, remove the battery module before mounting the unit in the rack.
Due to its weight, two people are required to remove the battery module.
The battery module is accessible from the front of
the UPS (shown at left).
This procedure requires a Phillips screwdriver.
1. If the UPS has been in operation, locate the white
cord
attached to the battery module connector
plug
. Grasp the cord and pull firmly toward
you until the connector plug is disconnected.
DO NOT pull the battery module cables.
If the UPS has not been in operation, the battery
will not yet be connected. The UPS ships with
the battery disconnected.
2. Use a screwdriver to remove the two battery
module mount screws located at the top corners
of the face plate
.
Set the screws aside in a safe place. You will re-
place them later.