16

N

OTE

: S

ETTING THESE ITEMS REQUIRES SOFTWARE OR OPTIONAL HARDWARE

.

F

UNCTION

F

ACTORY

D

EFAULT

U

SER

S

ELECTABLE

C

HOICES

D

ESCRIPTION

High Transfer
Point

120V Models
132 VAC

230V Models
253 VAC

120V Models
138, 135, 129 VAC

230V Models
264, 271, 280 VAC

To avoid unnecessary battery usage, set
the high transfer point higher if the
utility voltage is chronically high and
the connected equipment is known to
work under this condition.

Low Transfer
Point

120V Models
103 VAC

230V Models
196 VAC

120V Models
97, 100, 106 VAC

230V Models
188, 204, 208 VAC

Set the low transfer point lower if the
utility voltage is chronically low and
the connected equipment can tolerate
this condition.