Page 17

background image

15

4: U

SER

C

ONFIGURATION

I

TEMS

N

OTE

: S

ETTING THESE ITEMS REQUIRES SOFTWARE OR OPTIONAL HARDWARE

.

F

UNCTION

F

ACTORY

D

EFAULT

U

SER

S

ELECTABLE

C

HOICES

D

ESCRIPTION

Automatic Self-
Test

Every 14 days
(336 hours)

Every 7 days
(168 hours),
On Startup Only,
No Self-Test

This function sets the interval at which
the UPS will execute a self-test. Refer
to your software manual for details.

UPS ID

UPS_IDEN

Up to eight char-
acters to define
the UPS

Use this field to uniquely identify the
UPS for network management pur-
poses.

Date of Last Bat-
tery Replacement

Manufacture
Date

Date of Battery
Replacement

Reset this date when you replace the
battery module.

Minimum Capac-
ity Before Return
from Shutdown

0 percent

15, 50, 90 percent The UPS will charge its batteries to the

specified percentage before return from
a shutdown.

Sensitivity

Normal

Reduced, Low

Set lower than normal sensitivity to
avoid lowered battery capacity and
service life in situations where the con-
nected equipment can tolerate minor
power disturbances.

Duration of Low
Battery Warning

2 minutes

5, 7, 10 minutes

This function sets the time before shut-
down at which the UPS issues a low
battery warning. Set it higher than the
default if the operating system needs
more time for shutdown.

Alarm Delay
After Line Fail

5 second delay 30 second delay,

At Low Battery
Condition,
No Alarm

Set the alarm delay to avoid alarms for
minor power glitches.

Shutdown Delay

20 seconds

0, 80, 300, 600
seconds

This function sets the interval between
when the UPS receives a shutdown
command and when shutdown occurs.

Synchronized
Turn-on Delay

0 seconds

60, 180, 300 sec-
onds

The UPS will wait the specified time
after the return of utility power before
turn-on (for example, to avoid branch
circuit overload).