Unit configuration menu: “configuration – American Standard TRACER CH532 User Manual

Page 19

background image

2. Compressors timers
To access one of the parameters

displayed, press

and change

value using

or

. Confirm the

value by pressing

ACC 1st Start: Short cycle
compressor at first start (0 to 60 min
- factory setting: 2min)
ACC On-On: Short cycle between 2
starts of the same compressor (2 to
10 min - factory: 5 min)
Min On-On: Minimum time to add
compressor (5 to 240 s - factory
setting: 60s)
Min Off-Off: Minimum time to
remove compressor (1 to 120 s
factory setting 15s)

3. HP Control
To access one of the parameters

displayed, press

and change

value using

or

. Confirm the

value pressing

Fan Control: Fan type:

1 speed: 1 Speed fan
2 speed: 2 Speed fan
Invert: Inverter

Fan Ctrl StP: Fan control setpoint
(10 to 30 bar - factory setting: 15 bar)
Dead band Fan: Fans regulation
dead band (2 to 8 bar - factory
setting: 5 bar)

4. Control dead bands
To access one of the parameters

displayed, press

and change

value using

or

. Confirm the

value by pressing

Dead band Cmp: Compressors
regulation dead band around water
temperature (0.4 to 8.0°C - factory
setting: 3.0°C)
AntiFreeze: Cold water temperature
limit (-15 to 10°C - factory setting:
2°C)
Heater: Evaporator heater setpoint
according to ambient air
temperature (0 to 10°C - factory
setting: 3°C)

5. Winter Freeze Protection

Chilled water high limit: (15 to 25°C:
factory setting 15°C)
Water pump cycle OFF: (5 to 15 min:
factory setting 10min)
Winter Freeeze protection with
pump:

No

Heater or Ethylene

Glycol Required
Yes

Ctrl Pump Required

ACC 1st Start

2 min

ACC On-On

5 min

Min On-On

060 s

Min Off-Off

015 s

Fan control

1Speed

Fan Ctrl Stp

15.0 b

Dead band Fan

06.0 b

Dead band Cmp

03.0°C

Antifreeze

02.0°C

Heater

03.0°C

Unit configuration menu:
“Configuration”

CG-SV01B-E4

19

CW High Limit

15°C

Pmp Cycle OFF

10 min

WinFreezeProtPmp Yes
Ctrl Pump Required