2. ELECTRICAL SERVICE SPECIFICATIONS

A. Gas and Steam Models

IMPORTANT: Figures shown are for non-reversing models ONLY. For reversing models contact the

factory.

IMPORTANT: The dryer must be connected to the electric supply shown on the data label that is

affixed to the back side of the upper/top control door. In the case of 208 VAC or

230/240 VAC, the supply voltage must match the electric service specifications of

the data label exactly.

IMPORTANT: The wire size must be properly sized to handle the related current.

WARNING: 208 VAC and 230/240 VAC ARE NOT THE SAME. Any damage done to dryer

components due to improper voltage connections will automatically VOID THE

WARRANTY.

NOTE: ADC reserves the right to make changes in specifications at any time, without notice or

obligation.

MLG-75 (Gas)

MLS-75 (Steam)

E

LECTRICAL

S

ERVICE

S

PECIFICATIONS

(

PER DRYER

)

IMPORTANT: 208 VAC and 230/240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.

NOTE:

A. Fuse ratings are dual-element, time-delay, current limiting, class RK1 or RK5 ONLY.
B. Circuit breakers are thermal magnetic (industrial) type ONLY. For others, calculate/verify correct breaker

size according to appliance amp draw rating and type of breaker used.

C. Circuit breakers for 3Ø dryers must be 3-pole type.

SERVICE

VOLTAGE

PHASE

WIRE

SERVICE

APPROX.

AMP DRAW

MINIMUM

WIRE SIZE*

FUSING

Dual Element

Time Delay

CIRCUIT

BREAKER

120 (60 Hz)

1

2

13

10

20

25

208 (60 Hz)

1

2

8

14

12

15

208 (60 Hz)

3

3/4

5

14

8

15

240 (50/60 Hz)

3

3/4

5

14

8

15

240 (50/60 Hz)

1

2

7

14

12

15

380-400 (50 Hz)

3

3/4

3

14

5

15

416 (50 Hz)

3

3/4

3

14

5

15

460 (60 Hz)

3

3/4

3

14

5

15

* AWG Stranded Wire ... for individual lenghts less than 100 feet.