beautypg.com

American Power Conversion RT-UXICH User Manual

Page 4

background image

2

A

TTACH THE

B

EZEL TO THE

UPS

5000/6000

VA

XLI

MODELS

O

NLY

:

H

ARDWIRING

I

NSTRUCTIONS

Wiring must be performed by a qualified electrician.

Adhere to all national and local electrical codes.

Install a high magnetic 30/32 A utility circuit breaker

Use #10 AWG gauge (5sq. mm) wire.

1. Switch the utility circuit breaker OFF.
2. Remove the input access panel.
3. Remove circular knockout.


4. Run #10 AWG gauge (5sq. mm) wire through the access panel, and connect the wires to the

terminal block (Green: Ground, Brown: Hot, Blue: Neutral). Use an appropriate strain relief
(not included).

5. Replace the access panel.

This manual is related to the following products: