American Power Conversion RT-UXICH User Manual
Page 4
2
A
TTACH THE
B
EZEL TO THE
UPS
5000/6000
VA
XLI
MODELS
O
NLY
:
H
ARDWIRING
I
NSTRUCTIONS
•
Wiring must be performed by a qualified electrician.
•
Adhere to all national and local electrical codes.
•
Install a high magnetic 30/32 A utility circuit breaker
•
Use #10 AWG gauge (5sq. mm) wire.
1. Switch the utility circuit breaker OFF.
2. Remove the input access panel.
3. Remove circular knockout.
4. Run #10 AWG gauge (5sq. mm) wire through the access panel, and connect the wires to the
terminal block (Green: Ground, Brown: Hot, Blue: Neutral). Use an appropriate strain relief
(not included).
5. Replace the access panel.