American Power Conversion RT-UXICH User Manual

Page 12

background image

10

N

OTE

:

S

ETTINGS ARE MADE THROUGH SUPPLIED

P

OWER

C

HUTE SOFTWARE OPTIONAL

S

MART

S

LOT

ACCESSORY CARDS OR

T

ERMINAL

M

ODE

.

F

UNCTION

F

ACTORY

D

EFAULT

U

SER

S

ELECTABLE

C

HOICES

D

ESCRIPTION

High Bypass Point

+10% of
output voltage
setting

+5%, +10%, +15%,
+20%

Maximum voltage that the UPS
will pass to connected
equipment during internal
bypass operation.

Low Bypass Point

-30% of output
voltage setting

-15%, -20%, -25%, -30% Minimum voltage that the UPS

will pass to connected
equipment during internal
bypass operation.

Output Voltage

230 VAC

220, 225, 230, 240 VAC

Allows the user to select the
output voltage.

Output Frequency

Automatic
50 ± 3 Hz or
60 ± 3 Hz

Automatic
50 ± 3 Hz,
50 ± 0.1 Hz
60 ± 3 Hz
60 ± 0.1 Hz

Sets the allowable UPS output
frequency. Whenever possible,
the output frequency tracks the
input frequency.

Number of Batteries

1

Number of Connected
Batteries

Defines the number of
connected batteries for proper
run time prediction.
Default setting of 1 = 1920 VAh
(192 V x 10 Ah)
Setting of 2 = 3840 VAh, etc.