American Power Conversion RT-UXICH User Manual
Page 12
10
N
OTE
:
S
ETTINGS ARE MADE THROUGH SUPPLIED
P
OWER
C
HUTE SOFTWARE OPTIONAL
S
MART
S
LOT
ACCESSORY CARDS OR
T
ERMINAL
M
ODE
.
F
UNCTION
F
ACTORY
D
EFAULT
U
SER
S
ELECTABLE
C
HOICES
D
ESCRIPTION
High Bypass Point
+10% of
output voltage
setting
+5%, +10%, +15%,
+20%
Maximum voltage that the UPS
will pass to connected
equipment during internal
bypass operation.
Low Bypass Point
-30% of output
voltage setting
-15%, -20%, -25%, -30% Minimum voltage that the UPS
will pass to connected
equipment during internal
bypass operation.
Output Voltage
230 VAC
220, 225, 230, 240 VAC
Allows the user to select the
output voltage.
Output Frequency
Automatic
50 ± 3 Hz or
60 ± 3 Hz
Automatic
50 ± 3 Hz,
50 ± 0.1 Hz
60 ± 3 Hz
60 ± 0.1 Hz
Sets the allowable UPS output
frequency. Whenever possible,
the output frequency tracks the
input frequency.
Number of Batteries
1
Number of Connected
Batteries
Defines the number of
connected batteries for proper
run time prediction.
Default setting of 1 = 1920 VAh
(192 V x 10 Ah)
Setting of 2 = 3840 VAh, etc.