30

O

PERATING

S

TEAM

P

RESSURE

M

AXIMUM

125 psig

862 kPa

M

INIMUM

100 psig*

689 kPa

H

EAT

I

NPUT

(Normal Load)

7

Bhp

C

ONSUMPTION

(Approximate)

@

125

PSI

239

lbs/hr

108 kg/hr

Shaded areas are stated in metric equivalents.

* Minimum operating pressure for optimium results.

H. STEAM INFORMATION

It is your responsibility to have ALL plumbing connections made by a qualified professional to assure that the
steam plumbing installation is adequate and conforms with local and national regulations or codes.

Care must be exercised when leveling steam dryers into final position. After leveling the dryer, check the
downward pitch of the heat exchanger from front to rear with a level. Likewise, check the downward pitch of
the return condensate manifold toward its outlet part. Absence of these downward pitches will result in
probable water hammer and premature heat exchanger fracture and leakage.

The presence of condensate in the steam will cause water hammer and subsequent heat exchanger failure. The
steam supply connection must be taken from the top of a well-dripped steam main. If the supply run-out to the
dryer exceeds 20 feet (6 meters), it should be dripped just before the control valve with a proper trap and dirt
pocket.

IMPORTANT: Failure to comply with the requirements stipulated in this manual can result in

component failure which will VOID THE WARRANTY.

NOTE: The EURO-35 is manufactured with a pneumatic (piston) damper system which requires an

external supply of air 80 PSI +/- 10 PSI (5.5 bar +/- 0.7 bar).

1. Steam Coil PH Level

The normal PH level for copper type steam coils must be maintained between a value of 8.5 to 9.5. For
steel type steam coils the PH level must be maintained between a value of 9.5 to 10.5. These limits are set
to limit the acid attack of the steam coils.

IMPORTANT: Coil failure due to improper PH level will VOID THE WARRANTY.

2. Steam Requirements

3. Installation Instructions

To insure an adequate supply of steam is provided, be sure that the steam lines and steam return lines are
sized and laid out as stipulated in this manual. Inadequate steam lines and steam return lines or improper
steam plumbing will result in poor performance and can cause component failure. Clean, dry steam must
be
provided to the dryer.

IMPORTANT: Steam coil failure due to water hammer by wet steam will VOID THE WARRANTY.