1 Display
2 ADVANCE key
During operations, the current time is
shown in the display.

Press ADVANCE key for 5 to 6 sec-
onds. The display will show the first sta-
tus display from the list shown beloe.

To go to the next display, press once
again the ADVANCE key briefly.

If you do not press the ADVACE key for
some time, the display goes back to show-
ing the time.

The dosing pump must be ventilated if the
pump has sucked in air.

1 Dosing frequency button
2 Screw connections
3 Dosing pump

Stopping the WPC 5000 SW-AM: Dos-
ing pump switches off.

Fix cause for air suctioning, contact
customer service if necessary.

Loosen screws on the dosing pump.

Read and note the dosing frequency
that has been set at the LEDs of the
dosing pump.

Set the dosing frequency to 100% by
repeatedly pressing the dosing fre-
quency button and waiting until there
are no more bubbles in the suction pipe
(approx. 1 minute). Absorb the oozing
dosing liquid with a piece of cloth.

Tighten the screws.

Set the dosing pump to the original dos-
ing frequency.

1 Return key

Check the pressure difference between
the two manometers. Change filter inlay
if value is more that 0.08 MPa (0.8 bar):

Switch off the unit using the "ON/OFF"
key.

Turn the main switch to position "0"

WPC 5000 SW-AM:

1 Venting
2 Filter cover
3 Filter casing
4 Sample extraction tap (raw water)

1 Thumb screw
2 Filter candle

Take the pressure of the fine filter on
sample extraction tap (raw water).

Maintenance schedule

Time

Check / Activity

Target value

In case of deviation

daily

Filling level of dosing container

adequate filling

refill

Air bubbles in the dosing pipes

no air bubbles

Bleed dosing pump.

Drinking water flow based on the startup value

Lowered by less than 10%

Fine regulation

Drinking water guide value based on the startup
value

Increase within 10%

Fine regulation

Pressure difference between pump and concen-
trate pressure

maximum 15% above startup difference

Kärcher Customer Ser-
vice

Counter/meter for media and active carbon filters Reflushing has taken place in the last 24

hours

Kärcher Customer Ser-
vice

Pressure difference fine filter

maximum 0.08 MPa (0.8 bar)

Replace fine filter

Visual inspection of the plant

no leaks

Kärcher Customer Ser-
vice

weekly

Fill up operations log

monthly

Clean and rinse dosing container
Float switch in drinking water tank

no functional disruption can be detected

Kärcher Customer Ser-
vice

Maintenance Works

Check media and active carbon filters

Display

Significance

2000

Not important

0000

Not important

D–07

Number of days until the
next reflushing

–001

Number of reflushing that
have been conducted

0–01

days - hours since the last
reflushing

Bleed dosing pump.

Replace fine filter