# Description
Notes
42 remote reset release remote reset function input released.
43 trouble unsilence
all troubles unsilenced for all zones.
44 trouble silence
all troubles silenced for all zones.
45 supervisory unsilence all supervisory unsilenced for all zones.
46 supervisory silence
all supervisory silenced for all zones.
47 power-up reset
reset record when panel is powered up
48 external reset
reset record when external reset switch pressed or esd hit causes reset
49 remote reset active
remote reset switch activated
50 drill input restored
drill function input restore.
51 drill input active
drill function input present.
52 alarm unsilence
all alarm states unsilenced for all zones.
53 alarm silence
all alarm states silenced for all zones.
54 abort pressed
abort function input present.
55 abort released
abort function input restored.
56 palarm1 restore-----
device restored below pre-alarm1 threshold. analog data appended to this message
57 palarm1 active -----
device above pre-alarm1 threshold. analog data appended to this message
58 palarm2 restore-----
device restored below pre-alarm2 threshold. analog data appended to this message
59 palarm2 active -----
device above pre-alarm2 threshold. analog data appended to this message
60 alarm active -----
device has reached the alarm threshold. analog data appended to this message
61 manual alarm
manual pull function input present.
62 manual pre-discharge pre-discharge function input present.
63 manual release
manual release function input present.
64 waterflow active
waterflow input function activated.
65 waterflow restored waterflow input function restored to normal.
66 invalid abort active
abort switch pressed in zone without an alarm present
67 inv abort restored
abort switch released in zone without an alarm present
68 cfg resto 9: mr-----
config error #9 restored. zone number appended to this message.
69 cfg error 9: mr-----
config error #9: manual release is in an alarm only zone.
70 network reset
history stored when a reset command is recorded from cheetah net
71 network acknowledge history stored when an acknowledge command is recorded from cheetah net
72 process restored
process state for this zone de-activated.
73 process present
process state for this zone activated.
74 trouble restored
trouble state for this zone de-activated.
75 trouble present
trouble state for this zone activated.
76 supervisory restored supervisory state for this zone de-activated.
77 supervisory present supervisory state for this zone activated.
78 drill restored
drill state for this zone de-activated.
79 drill present
drill state for this zone activated.
80
net
member#a
missing
network member #a is missing.
81 net member#a return network member #a has returned on line.
82 net manager missing network manager is missing.
83 net manager return network manager has returned on line.