- Refer to blueprints:

-

Main electrical panel diagram

-

Tumbler junction box wiring diagram

-

Rear panel controls wiring diagram

-

Re-test

0 UNLOAD 1 Selection

e)

PROBABLE CAUSES;

1. Rear panel disconnect plug

2. Defective switch

3. Wiring back to main electrical enclosure

f)

POSSIBLE SOLUTIONS;

1. If the O UNLOAD 1 switch doesn’t respond when selected:

-

Verify that the rear panel controls disconnect plug is indeed connected. This disconnect plug
allows for the removal of the rear control panel for dryer servicing.

2. Defective O UNLOAD 1 Selector Switch

-

Shut power off at the main breaker and remove the rear panel and check switches using an OHM
meter; replace if defective.

3. Wiring back to the main electrical enclosure

-

With the control voltage “ON” Front Panel “GREEN” Button

-

Select “1” on the “O UNLOAD” switch located on the rear control panel. Does PLC
(Programmable Logic Controller) IN PIN 19 = UNLOAD, REAR PANEL light?

- If “YES,” refer to section 3a

- If “NO”, refer to section 3b

3a) The L.E.D. (light emitting diode) “ON” on the PLC (Programmable Logic Controller) indicates are

also illuminating when the O UNLOAD 1 selector switch is on “1.”

PLC OUT PIN 7 = UNLOAD DOOR (OPEN)

PLC OUT PIN 10 = FRONT UP

-

If output indicators are functional, however the UNLOAD DOORS of FRONT UP commands
are not executed correctly: