2

A

TTACH THE

B

EZEL TO THE

UPS

H

ARDWIRING

I

NSTRUCTIONS

5000

VA

MODELS

O

NLY

:

Wiring must be performed by a qualified electrician.

Adhere to all national and local electrical codes.

Install a high magnetic 30/32 A utility circuit breaker

Use #10 AWG gauge (5 mm

2

) wire.

1. Switch the utility circuit breaker OFF.
2. Remove the input access panel.
3. Remove circular knockout.


4. Run #10 AWG gauge (5 mm

2

) wire through the access panel, and connect the wires to the

terminal block (Green: Ground, Brown: Hot, Blue: Neutral). Use an appropriate strain relief (not
included).

5. Replace the access panel.