American Power Conversion UXI/UXICH User Manual
Page 12

10
N
OTE
:
S
ETTINGS ARE MADE THROUGH SUPPLIED
P
OWER
C
HUTE SOFTWARE
,
OPTIONAL
S
MART
S
LOT
ACCESSORY CARDS
,
OR
T
ERMINAL
M
ODE
.
F
UNCTION
F
ACTORY
D
EFAULT
U
SER
S
ELECTABLE
C
HOICES
D
ESCRIPTION
Low Bypass Point
160 VAC
Output Voltage Setting
200 VAC:
160 - 185 VAC
208 VAC:
160 - 190 VAC
220 VAC:
160 - 195 VAC
230 VAC:
160 - 200 VAC
240 VAC:
160 - 205 VAC
Minimum voltage that the UPS
will pass to connected
equipment during internal
bypass operation.
Output Voltage
230 VAC
200, 208, 220,
230, 240 VAC
Allows the user to select the
on-line output voltage.
50 ± 3 Hz
50 ± 1 Hz
50 ± 0.1 Hz
60 ± 3 Hz
60 ± 1 Hz
60 ± 0.1 Hz
Output Frequency
Automatic
50 ± 3 Hz or
60 ± 3 Hz
50 ± 3 Hz or 60 ± 3 Hz
Sets the allowable UPS output
frequency. Whenever possible,
the output frequency tracks the
input frequency.
Total Battery
Capacity
0
0 to 1000 A h
Defines the Amp hours of
connected battery for proper run
time prediction.
Bypass Acceptable
Not required
Required/ Not required
Phase and frequency lock
required/not required before the
UPS will switch to bypass.