American Power Conversion UXI/UXICH User Manual

Page 12

background image

10

N

OTE

:

S

ETTINGS ARE MADE THROUGH SUPPLIED

P

OWER

C

HUTE SOFTWARE

,

OPTIONAL

S

MART

S

LOT

ACCESSORY CARDS

,

OR

T

ERMINAL

M

ODE

.

F

UNCTION

F

ACTORY

D

EFAULT

U

SER

S

ELECTABLE

C

HOICES

D

ESCRIPTION

Low Bypass Point


160 VAC

Output Voltage Setting
200 VAC:

160 - 185 VAC
208 VAC:
160 - 190 VAC
220 VAC:
160 - 195 VAC
230 VAC:
160 - 200 VAC
240 VAC:
160 - 205 VAC

Minimum voltage that the UPS
will pass to connected
equipment during internal
bypass operation.

Output Voltage

230 VAC

200, 208, 220,
230, 240 VAC

Allows the user to select the
on-line output voltage.

50 ± 3 Hz
50 ± 1 Hz
50 ± 0.1 Hz

60 ± 3 Hz
60 ± 1 Hz
60 ± 0.1 Hz

Output Frequency

Automatic
50 ± 3 Hz or
60 ± 3 Hz

50 ± 3 Hz or 60 ± 3 Hz

Sets the allowable UPS output
frequency. Whenever possible,
the output frequency tracks the
input frequency.

Total Battery
Capacity

0

0 to 1000 A h

Defines the Amp hours of
connected battery for proper run
time prediction.

Bypass Acceptable

Not required

Required/ Not required

Phase and frequency lock
required/not required before the
UPS will switch to bypass.