SDM-CD8S 8 Channel Solid State DC Control Module
6. Datalogger Instructions
6.1 CRBasic Dataloggers (CR800, CR850, CR1000, CR3000,
CR5000, CR9000(X))
The SDMCD16AC instruction is used to control the SDM-CD8S and all 
versions of the SDM-CD16. 
SDMCD16AC (Source, Reps, SDMAddress)
Remarks
A port on an SDM-CD8S is enabled/disabled (turned on or off) by sending a 
value to it using the SDMCD16AC instruction. A non-zero value will enable 
the port; a zero value disables it. The 16 values to be sent are held in the 
Source array or long integer. The SDM-CD8S only uses the first 8 values to 
set its 8 ports. 
The SDMCD16AC instruction has the following parameters:
Source
The Source parameter is an array (dimensioned as Float, 
Long, or Boolean) or a single long integer which holds the 
values that will be sent to the SDM-CD8S to enable/disable 
its ports. An SDM-CD8S has 8 ports; therefore, in most 
instances the source array should be dimensioned to 8 times 
the number of Repetitions (the number of SDM-CD8S 
devices to be controlled). As an example, with the array 
CDCtrl(16), the value held in CDCtrl(1) will be sent to port 
1, the value held in CDCtrl(2) will be sent to port 2, etc. 
The value held in CDCtrl(32) would be sent to port 8 on the 
second SDM-CD8S. 
 
If the Source parameter is defined as a Long variable, but it 
is dimensioned less than 16 * Reps, Source will act as a 
binary control for the instruction whose bits 0..15 will 
specify control ports 1..16, respectively. In this instance, 
Source(1) will be used for the first rep, Source(2) will be 
used for the second, and so on. The SDM-CD8S only 
responds to the first 8 bits sent. 
Reps
The Reps parameter is the number of SDM-CD8S devices 
that will be controlled with this instruction. 
SDMAddress
The SDMAddress parameter is used to define the address of 
the SDM-CD8S that will be controlled with this instruction. 
Valid SDM addresses are 0 through 14. Address 15 is 
reserved for the SDMTrigger instruction. If the Reps 
parameter is greater than 1, the datalogger will increment the 
SDM address for each subsequent device that it 
communicates with. 