Operation, 1 wiring, Wiring – Campbell Scientific CS526 ISFET pH Probe User Manual

Page 14: 1. wiring

background image

CS526 ISFET pH Probe

Operating

Temperature:

10° to 40°C

Water Pressure:

0 to 700 kPa (0 to 101.5 psi)

Power Requirement

Source:

5 Vdc

Load:

15 mA maximum

Output:

TTL logic, 2400 bps

8 data bits, no parity, 1 stop bit

Maximum Cable Length:

100 m (328 ft)

Cable Type:

Three-twisted pair, 24-AWG cable with

Santoprene

jacket

Sensor Material:

PEEK

Weight

w/10-ft cable:

318 g (11.2 oz)

Dimensions

Length:

102 mm (4 in)

Diameter:

16 mm (0.63 in)

Certifications:

ISO 9001

compliant

EMC standard IEC61326:2005

7. Operation

If you are programming your datalogger with Short Cut, skip Section 7.1,

Wiring, and Section 7.2, Datalogger Programming. Short Cut does this work

for you. See Section 4, Quickstart, for a Short Cut tutorial.

7.1 Wiring

TABLE 7-1. Wiring

Wire Color

Wire Label/Function Datalogger Connections

Red (see following

caution)

Power 5V

5V

Black

Ground

G

White

Signal #1 (Rx)

Control Port (Tx)

Green

Signal #2 (Tx)

Control Port (Rx)

Clear

Shield

G

This probe must be connected to the datalogger’s 5 V

terminal (

not 12 V). Connecting to a higher voltage will

damage the probe beyond repair.

CAUTION

6