Campbell Scientific 253-L and 257-L (Watermark 200) Soil Matric Potential Sensors User Manual
Page 31
253-L and 257-L Soil Matric Potential Sensors
;{CR10X}
01: 30.0000 Execution
Interval
(seconds)
;Turn on AM16/32
1: Do (P86)
1: 41
Set
Port
1
High
;Loop to measure five 107 probes and five 253's
2: Beginning of Loop (P87)
1: 0
Delay
2: 5
Loop
Count
;Advance to next multiplexer channel
3: Do (P86)
1: 72 Pulse Port 2
;10 msec delay to allow switch to settle
4: Excitation with Delay (P22)
1: 1
Ex
Channel
2: 0
Delay W/Ex (0.01 sec units)
3: 1
Delay After Ex (0.01 sec units)
4: 0
mV
Excitation
;Measure soil temperature
5: Temp (107) (P11)
1: 1
Reps
2: 1
SE
Channel
3: 1
Excite all reps w/E1, 60Hz, 10ms delay
4: 1
-- Loc [ T107_C_1 ]
5: 1.0
Multiplier
6: 0.0
Offset
;Measure 253 sensor
6: AC Half Bridge (P5)
1: 1
Reps
2: 14
250 mV Fast Range
3: 2
SE
Channel
4: 2
Excite
all
reps
w/Exchan
2
5: 250
mV
Excitation
6: 11
-- Loc [ kOhms_1 ]
7: 1
Multiplier
8: 0
Offset
;Convert Half Bridge reading to resistance (k-Ohm)
7: BR Transform Rf[X/(1-X)] (P59)
1: 1
Reps
2: 11
-- Loc [ kOhms_1 ]
3: 1
Multiplier
(Rf)
;Apply nonlinear equation from 5.3.2
8: Z=X*Y (P36)
1: 1
-- X Loc [ T107_C_1 ]
2: 1
-- Y Loc [ T107_C_1 ]
3: 6
-- Z Loc [ WP_kPa_1 ]
25