7. wiring for programming example #3 – Campbell Scientific 253-L and 257-L (Watermark 200) Soil Matric Potential Sensors User Manual
Page 29

253-L and 257-L Soil Matric Potential Sensors
TABLE 7-7. Wiring for Programming Example #3
CR1000 AM16/32 Sensor
Wire
Function
12V 12V
G GND
C1 RES
C2 CLK
VX1 or EX1
COM ODD H
SE1 (1H)
COM ODD L
Ground COM
GROUND
SE2 (1L)
COM EVEN H
Ground
COM EVEN L
1000 ohm
resistor from
SE2 to EX2
1H 107
Black
Excitation
1L
Red
Positive
Signal
GROUND
Purple
Negative
Signal
GROUND
Clear
Shield
2H 253
White
Positive
Signal
2L
Black
Negative
Signal
GROUND
Clear
Shield
Continue wiring sensors to multiplexer with 107 probes
attaching to odd numbered channels and 253 sensors to even
numbered channels.
AM16/32 in 4x16 mode.
‘CR1000
Public T107_C(5), WP_kPa(5), kOhms(5)
Dim i
Units T107_C()=Deg C
Units kOhms=kOhms
Units WP_kPa=kPa
DataTable(Hourly,true,-1)
DataInterval(0,60,Min,10)
Average(5, T107_C, FP2, 0)
Sample(5, WP_kPa, FP2)
Sample(5, kOhms, FP2)
EndTable
BeginProg
Scan(60,Sec, 3, 0)
PortSet(1,1) 'Turn AM16/32 Multiplexer On
Delay(0,150,mSec)
i = 1
SubScan (0,uSec,5)
PulsePort(2,10000)
'Soil temperature measurement
Therm107(T107_C(i),1,1,VX1,0,250,1,0)
'253 Soil Moisture Sensor measurements
BrHalf(kOhms(i),1,mV250,2,VX2,1,250,true,0,250,1,0)
23