3-4-2. Connect AC output and AC input wiring to the ST series terminals.

Please take the following information as your reference.

Terminal Wire

color

Wire length / gauge

ST1000&ST1500

ST2000&ST2500

AC

OUTPUT

Line (L)

Black

Within 16 feet / AWG#

14~16

26~32 feet / AWG#

12~14

Within 16 feet / AWG#

10 ~12

26~32 feet / AWG#

8 ~10

Neutral (N)

White

AC INPUT

Line (L)

Brown

Neutral (N)

Blue

Ground

Green / Yellow

or Bare

copper

3-4-3. Please double check and review all connections to ensure

the wires are in correct terminals and the connections are tight.

3-4-4.

Before connecting AC output and AC input terminals of the ST series,

you can either use front compartment cover or a side hole to coil out.
Both AC input and AC output are coiled out from the front compartment
cover when in production. If you want to change the position, you
should open the top cover first, and then switch the wire of the front
compartment cover and the plastic cover of the side of top cover.