3-2. Protections Features

Model

DC Input (VDC)

Over Temperature Protection

Over Voltage Under

Voltage

Alarm

Under Voltage

INTERIOR

HEAT SINK

Shut-
down

Restart

Shut-
down

Restart Shut-

down

Restart Shut-

down

Restart

12V 15.3 14.3 11.0 10.2

12.7

70℃

45℃ 90℃

60℃

24V 30.6 28.6 22.0 20.3

25.2

48V 61.2 57.2 44.0 40.8

49.7

3-3 DC Wiring Connections

Follow the instructions to connect the battery cables to DC input terminals of
the Inverter. The cable should be as short as possible (less than 6 feet / 1.8
meters ideally) so that it can handle the required current in accordance with
the electrical codes or regulations application. Inappropriate length of cables
will deteriorate the inverter performance such as poor surge capability,
frequent low-input voltage warnings, and shutdown. UVP warning occurs
when DC voltage drops across the cables from the inverter to the batteries.
The longer or narrower the cables, the more the voltage drop.

I

ncreasing your DC cable size will help improve the situation.

The following recommended cables are for the best performance of the
inverter. (Apply both 120V and 230V versions)

Model No

Wire AWG

Inline Fuse

ST1000-112 / 212

# 2

150 A

ST1000-124 / 224

# 4

80 A

ST1000-148 / 248

# 6

40 A

ST1500-112 / 212

# 2

200 A

ST1500-124 / 224

# 4

100 A

ST1500-148 / 248

# 6

50 A

ST2000-112 / 212

# 2/0

250 A

ST2000-124 / 224

# 1/0

125 A

ST2000-148 / 248

# 2

70A

ST2500-112 / 212

# 4/0

400 A

ST2500-124 / 224

# 2/0

200 A

ST2500-148 / 248

# 1/0

100 A