beautypg.com

Ashcroft D700 - Differential Pressure Switches User Manual

Page 2

background image

INSTALLATION

These controls are precision instruments and should never be
left with internal components exposed. After installation ensure
that covers are in place and conduit openings are closed.

MOUNTING D400 AND D700 SERIES

There are three holes external to the enclosures for surface
mounting. The locations of these holes is shown on the general
dimension drawing. The controls may also be mounted directly
on the pressure line using the pressure connections.

ELECTRICAL CONNECTIONS

Remove cover

D400 Series – two screws hold cover to enclosure

D700 Series – cover unscrews

CONDUIT CONNECTIONS

Note – It is recommended that Teflon

®

tape or other sealant be

used on conduit, bushing or plug threads to ensure integrity of
the enclosure.

D400 Series standard – one

3

4

NPT conduit hole right side.

D700 Series standard – two

3

4

NPT conduit holes with one

permanent plug.

NEMA 7 & 9 enclosures require proper conduit

seals and breathers as per the National Electrical Code.

D400 & WT700 Series – XJL variation – two

3

4

NPT conduit

holes with two

3

4

to

1

2

NPT reducing bushings.

D400 Series – XJK variation – two

3

4

NPT conduit holes.

D400 SERIES

SPDT – Wire directly to the switch according to circuit require-

ments. On controls with pilot lights, wire lights according to cir-
cuit diagram on the inside of the cover. See special wiring
instruction tag for single switches with two pilot lights and dual
switches with one or more pilot lights.

2-SPDT – Dual switching elements consist of two SPDT switches

mounted together in a bracket. The switches are calibrated to have
simultaneous operation within 1% of range either on increasing
or decreasing pressure, but not in both directions. Wire directly
to the front and rear switch according to circuit requirements.
Leads provided on rear switch and leads provided for hermeti-
cally sealed switch components are color coded as follows:
Common

– White

Normally Closed – Red
Normally Open

– Blue

See SPDT instructions for pilot light hook-up.

Installation and Maintenance Instructions for

D400 & D700 ASHCROFT

®

Snap Action

Switches for Differential Pressure Control

D700 SERIES

SPDT – Wire directly to the switch according to circuit

requirements.

2-SPDT – Wire to front switch terminal block (left) and rear

switch terminal block (right) as marked. Strip insulation

5

16

˝,

insert in proper terminal connector and tighten clamping screw
to secure.

ADJUSTMENT OF SETPOINT

D400 & D700 Series – A single setpoint adjustment nut (

7

8

˝) is

located centrally at the bottom on the inside of the enclosure.
The direction of turning is indicated on a label affixed to the
inside of the control enclosure.
A typical calibration procedure would be as follows:

Static Working Pressure

– 600 psig

Adjustable Differential Range – 30/200 psid
Differential Setpoint

– 150 psi above static working

pressure

Simultaneously raise the high and low side pressure to 600
psig. Maintain the low side pressure at 600 psig. Raise the high
side pressure to 750 psig to obtain 150 psi differential.

Turn the adjustment nut until the switch changes mode at 150
psi differential. When the setpoint has been achieved, raise and
lower the high side pressure to ensure that the differential set-
point is correct.

D450 and D750 VARIABLE DEADBAND SWITCHES

Deadband is varied by rotating the wheel on the precision
switch. When viewed from the front of the enclosure, rotation to
the left increases deadband – rotation to the right decreases
deadband. Letters on the wheel may be used as a reference.
Deadbands obtainable will vary from 2% to 9% of pressure
range depending on range segment and the type of diaphragm.

ADJUSTMENT OF SETPOINT

As received, the differential pressure switch will normally be set
to approximately 90% of range. Rotate the wheel on the MICRO
SWITCH all the way to the right. This will provide the smallest
deadband. Pressurize the system to the required setpoint and
turn the adjustment nut until the switch changes mode. Lower
the pressure to reset the switch. Rotate the wheel on the
MICRO SWITCH until the desired deadband is obtained. The
upper setpoint will be changing upward with this adjustment.
Lower the pressure to reset the switch. Increase the pressure to
the desired setpoint and turn the adjustment nut until the switch
changes mode. Lower the pressure and check the reset point
and deadband.

Note – As indicated above, adjustment of setpoint is made by

use of

7

8

˝ nut. The precision switch element mounting screws

and bracket adjusting screw are factory sealed and should not
be tampered with.

© 2012 Ashcroft Inc., 250 East Main Street, Stratford, CT 06614-5145, USA, Tel: 203-378-8281, Fax: 203-385-0499, www.ashcroft.com
All sales subject to standard terms and conditions of sale. I&M009-10007- (250-2248E) 10/12

TERMINAL BLOCK
FRONT SWITCH

TERMINAL BLOCK
REAR SWITCH

NC

NO

C

NC

NO

C

This manual is related to the following products: