SPECIFICATIONS
ELECTRICAL
Input
Voltage
120VAC +35%, -20% (without Battery discharge)
Frequency
60Hz or 50Hz
Current
25A max @ 120Vac
Output
Voltage 120VAC
+3%
Frequency
60Hz or 50Hz +.25% (software selectable)
Current 20A
(2400VA)
Crest Factor Ratio
(Non-linear load and
less than 5% THD) Typical
@50% Load Up to 4.8:1
@75% Load Up to 3.2:1
@100% Load Up to 2.4:1
Harmonic Distortion
5% Max. THD
Dynamic Response
+4% for 100% Step Load Change, 0.5 Millisecond Recovery Time
Overload
110% for 10 Minutes; 200% for 50 milliseconds
Efficiency (UPS)
Load Power Factor
85%
0.7
UPS Protection
Input and Output Short Circuit; Input and Output Overload;
Excessive Battery Discharge
MECHANICAL
Input
CPC Type 3 position Inlet connectors
Output
CPC Type 37
position reversed sex Connector
Overall Dimensions L x H x W
23 in x 5.25 in x 19 in. (58.4 cm x 13.3 cm x 48.3 cm)
Weight
120 lb. (54.4 kg)
Cooling
Low Velocity, Forced Air
CONTROLS AND INDICATORS
Visual Indicators
Battery Level, Load Level, Battle short
AC Input AC Output Battery On Bypass On
Cold Start Fault Replace Battery
Audible Alarms
Utility Interrupt, Inverter Failure, Overload, Low Battery, fan fail, warm and
overtemp.
Intelligent Computer Interface
(DB-25F)
Full Interactive, Remote Computer Monitoring and Control of
UPS Functions (RS232 Interface);
Open-collector Alarm Signals interface to control panel
DESIGN
Standard Features Regenerative
TM
On-Line, Sinewave Inverter Powers Load Continuously
Extended Brownout Protection, External Battery Connector, High
Frequency, Digitally Controlled IGBT PWM, Power Factor Corrected on
Input, Designed for Non-linear Loads, Continuous Operation on +35%
Line, 2400VA: ?Min. Backup @ 1680 watts / ? Min. @840 watts
ENVIRONMENTAL
Operating Temperature
32
o
F to 122
o
F (0
o
C to 60
o
C)
Humidity
0% to 95% non-condensing
Altitude
Sea Level to 10,000 Feet