BATTERY RECYCLING
• The batteries used in this equipment are recyclable. Proper disposal is required and mandated
by law. The batteries contain lead and pose a hazard to the environment and human health if
not dispose of properly.
• Refer to local codes for proper disposal requirements or return the batteries to the factory.
• ALWAYS contact the factory for information concerning shipment, disposal, or replacement of
batteries.
Table 15
: PREVENTIVE MAINTENANCE SCHEDULE
Item
Schedule
Actions
Cleaning
6 Mos.
Blow out unit with air.
Battery
6 Mos.
Clean terminals and check for corrosion.
Fans
6 Mos.
Check for proper operation.
5.3
Trouble Analysis
Unit does not power up:
• Make sure AC & DC input connectors are connected and seated properly.
• Check front panel circuit breakers
• Check Bypass Box for proper installation and wiring.
• Check Bypass Box to be switched to the “UPS” position.
No Backup when utility power is lost:
• Make sure DC breaker is in the “ON” position.
• If Bypass switch is installed, make sure it is in the “UPS” position.
• Check Batteries.
On turn on, Unit goes through startup sequence then goes into alarm and inverter does not turn on:
• Possible bad inverter.
• Load on unit may be over Max. rating.
Unit in Alarm, but is still operating OK:
• Possible over temp.
• Check fans in the unit to make sure they are running.