2 specifications, Table 4: electrical specifications, Input specification – Clary SP1250LX User Manual
Page 15: Output specification
15
2.2 Specifications
The various specifications of the UPS system are provided in the following tables.
Table 4: ELECTRICAL SPECIFICATIONS
Electrical Specifications
Input Specification
Nominal Input Voltage
120 VAC, Single Phase
Input Voltage Range
75 VAC to 155 VAC
Input Frequency
45 to 65 Hz (+/- 5%)
Input Configuration
3 Wire (Hot, Neutral & Ground)
Input Protection
Input breaker 20 amps, SP2000LX 30A
Output Specification
Nominal Output Voltage
120 VAC, Single Phase
Power Rating
1.25 KVA (1250VA/875W), 2 KVA (2000VA/1400W)
Output Voltage Regulation
+/- 4% for 100% step load change and from
High battery to Low battery condition
Output Frequency
50 or 60 Hz (+/- .5%) unit not in sync.
Output Configuration
3 Wire (Hot, Neutral & Ground)
Output Wave Form
True Sine wave
Overload capability
110% for 10 minutes 200% for 50 milliseconds
2k PLUS 160% for 10 seconds
Fault clearing
Current limit and automatic shutdown
Short circuit protection
Current limit and automatic shutdown
Efficiency
85% at full load (on utility)
Load Power Factor
.7 lagging through unity to .7 leading