Table 12: list of rules – Clary SP1250LX User Manual
Page 35

35
Table 12: LIST OF RULES
#
Rule
Description
Parameters
00
Relay Off
Turns Relay OFF.
None
01
On_Bat
Activates when UPS is on
Battery Mode.
None
02
Low_Bat_1
Activates when batteries reach
user settable capacity level.
Set battery capacity in %
Limits 0% - 100%, Resolution 1%
03
Bat_Timer_1
Activates after user settable
time when UPS is in Battery
mode.
Set Timer in HH:MM:SS
Limits 00:00:00 – 18:12:15, Resolution 1 Second
04
Alarms_1
Activates when Alarm
conditions occur.
See Alarm/Fault Table
Allows you to choose which alarms you want to
activate this condition. You may choose all or just
some.
05
Faults_1
Activates when Fault
conditions occur.
See Alarm/Fault Table
06
Low_Bat_2
Additional Low_Bat condition.
Functions same as Low_Bat_1.
Set battery capacity in %
Limits 0% - 100%, Resolution 1%
07
Bat_Timer_2
Additional Bat_Timer
condition. Functions same as
Bat_Timer_1.
Set Timer in HH:MM:SS
Limits 00:00:00 – 18:12:15, Resolution 1 Second
08
Alarms_2
Additional Alarm condition.
Functions same as Alarms_1.
See Alarm/Fault Table
09
Faults_2
Additional Fault condition.
Functions same as Faults_1.
See Alarm/Fault Table
10
Low_Bat_3
Additional Low_Bat condition.
Functions same as Low_Bat_1.
Set battery capacity in %
Limits 0% - 100%, Resolution 1%
11
Bat_Timer_3
Additional Bat_Timer
condition. Functions same as
Bat_Timer_1.
Set Timer in HH:MM:SS
Limits 00:00:00 – 18:12:15, Resolution 1 Second
12
Alarms_3
Additional Alarm condition.
Functions same as Alarms_1.
See Alarm/Fault Table
13
Faults_3
Additional Fault condition.
Functions same as Faults_1.
See Alarm/Fault Table
14
Fan_Ctrl_1
Activates at Temperature
levels set by user.
Set Hi/Lo limits. Choose from internal sensor or
external(Aux) sensor. There is a minimum Five°C
differential limit between the HI and Low limts.
Limits 0˚C - 125˚C, Resolution 1˚C
15
Fan_Ctrl_2
Additional Fan Control
condition.
Set Hi/Lo limits. Choose from internal sensor or
external(Aux) sensor. There is a minimum Five°C
differential limit between the HI and Low limts.
Limits 0˚C - 125˚C, Resolution 1˚C