Table 9: clary outposttm batteries – Clary SP1250LX User Manual
Page 17

17
Table 9:
CLARY OutPost
TM
BATTERIES*
Estimated Runtime
(Per set @ 77°F / 25°C)
(New Batteries, fully
charged)
Unit
Weight
Overall Dimensions
Per Battery Inches (cm.)
Clary
Part. No.*
Volts/
A-hrs.
300
Watts
500
Watts
700
Watts
875
Watts
Lbs.
(Kg.)
Length
L
Width
W
Height
H
OP72C
(Set of
6
Batteries)
12
VDC/
41 AH
6.3
Hrs.**
3.8
Hrs.**
2.5
Hrs.**
1.8
Hrs.**
29
(13.2)
7.68
(19.6)
5.15
(13.1)
7.9
(20.1)
Clary
Part. No.*
Volts/
A-hrs.
300
Watts
700
Watts
1050
Watts
1400
Watts
OP96C
(Set of 8
Batteries)
12
VDC/
41 AH
8.5
Hrs.**
3.5
Hrs.**
1.5
Hrs.**
1.0
Hrs.**
*OP72C battery sets include six (6) batteries per set. Wired in series, each set provides 72 VDC.
*OP96C battery sets include eight (8) batteries per set. Wired in series, each set provides 96
VDC.
** Actual times may vary, runtimes are dependent on many factors.
Lower/Higher AH capacity batteries, allowing less or more runtime, are available on special order.
Contact factory for more information.
Communications, Controls & Diagnostics
Optional TCIP/Ethernet available, contact factory for more information.
Front Panel controls: Power ON, Cold (DC) Start, Alarm Silence, Battery Test, Bypass Circuit
Breaker, and DC/Battery Circuit Breaker.
Options
Battery Tray to hold three (3) OP72C batteries is 19” wide for use in 170 type cabinets and
mounts on standard RETMA rails.
Swing-out Battery Box, mounts on right rail inside back door of 170 type cabinets. Box is designed
to hold tree (3) OP72C batteries
External Temperature Sensor (SPD-16H1)