Condensate discharge temperature limiter
5.3 Controller adjustment
(see Fig. 3 page 7)
- The factory setting is such that the discharge valve reaches its closing position at a
temperature of approx. 116°C.
- The controller (Pos. 24) is factory set as ordered by the customer.
It can subsequently be reset as follows without dismantling the screw cap (Pos. 6):
- Open the plug (Pos. 43) when unpressurised
- Use a screwdriver to adjust the closing temperature direct from the outside (half a
clockwise rotation of the spindle (Pos. 24.3) gives a temperature rise of approx. 7 K.)
- Screw in and tighten plug (Pos. 43) (see 7.4).
5.4 Steam trap testing through ultrasonic measurement
Testing the operation of the steam trap in the installed state is straightforward with the
“ARImetec
®
-S” multifunction tester.
Refer to data sheet „ARImetec
®
-S“.
5.5 Installation position
The steam trap can be installed in any position except screw cap (Pos. 6) down.
Note installation position relative to flow, see mark on valve.
ATTENTION !
- refer to item 10.0 and 11.0 prior to dismantling and repair work!