ARI Armaturen Condensate PN40 EN User Manual
Page 10
Page 10
Rev. 0040807001 2404
Operating and installation instructions
Condensate discharge temperature limiter
Series 647:
- Unscrew strainer plug (Pos. 8), remove strainer sleeve (Pos. 7) and clean parts / seal
faces.
- Fit strainer sleeve (Pos. 7), making sure seal faces are clean.
- Tighten strainer plug (Pos. 8) (see 7.4).
Version with plug-in thermometer:
- Unscrew thermometer adapter (Pos. 47) with thermometer (Pos. 48) and clean parts / seal
faces.
- Fit thermometer adapter (Pos. 47), making sure seal faces are clean
- Tighten thermometer adapter (Pos. 47). (see 7.4).
- Assemble in reverse order (see 7.4).
7.2 Option blow down valve
7.3 Option thermometer adapter with thermometer
ATTENTION !
Escape of hot medium under pressure !
Observe item 2.2 !
Accumulated dirt can be blown out of the strainer sleeve
(Pos. 7) by opening the pressure screw (Pos. 46.1) of the
blow down valve.
When opening, hold against strainer plug (Pos. 46).
During operation it is imperative to observe general working
safety conditions and possibly fit devices to guard against
scalding/injury.
Note section 7.4 when installing and operating the option.
Fig. 4
It is possible to check the process temperature in situ with the
thermometer (Pos. 48).
Note section 7.4 when installing and operating the option.
Fig. 5