Operating and installation instructions

CONA

®

TD - Thermodynamic steam traps

9.0 Troubleshooting table

ATTENTION !
- refer to item 10.0 and 11.0 prior to dismantling and repair work!
- refer to item 6.0 before restarting the plant!

Fault

Possible cause

Corrective measures

No flow

Installed in wrong flow direction

Fit valve in direction of flow arrow

Flange covers not removed

Remove flange covers

Little flow

Strainer clogged (Pos. 2)

Clean / change strainer;
refer to item 7.1

Piping system clogged

Check piping system

Changed upstream pressure or back
pressure operating conditions

Correct selection acc. to flow diagram

No closure, or internal
leakage

Controller (Pos. 24) clogged

Clean strainer and controller;
refer to item 7.1

Controller worn out

Replace controller or valve;
refer to item 7.1

Controller (Pos. 24) incorrectly screwed
into body

Check seal face between body and
controller, tighten controller correctly,
refer to item 7.3

External leakage

Sealing cap (Pos. 6) or system
connection with hex. nuts (Pos. 27) not
properly tightened

Tighten; refer to item 7.3

Seals (Pos. 11 and 17) defective

Replace seals; refer to item 7.1