Operating and installation instructions

3-way/str.thr. control valves - WA206/216/306/316

7.0 Care and maintenance

7.1 Replacement of stem sealings

If the stem starts leaking, the sealing is worn out and must be replaced.

- Remove actuator. (Refer to operating instructions for actuator!)
- Unscrew worn stem sealing (pos. 8) from the body (pos. 1) and pull it off the stem (pos. 7).
- Check valve stem (pos. 7) for deposits and damage; if possible, remove with fine polishing

linen.

- Otherwise the stem (pos. 7) must be replaced (for description refer to item 7.2), since a

new sealing will soon start leaking again if the stem is damaged.

- Carefully push the new stem sealing (pos. 8) – factory-greased – onto the stem (pos. 7).

- Screw tightly into position
Tightning torques for stem seal:

ATTENION !
Refer to item 10.0 and 11.0 before dismantling the valve.

DN

Torque

15 - 50

70 Nm

65 - 150 145 Nm

Fig. 6: WA306H, WA316H

Fig. 7: WA306R