8.0 Troubleshooting
In the event of malfunction or faulty operating performance check that the installation and
adjustment work has been carried out and completed in accordance with these Operating
Instructions.
If malfunctions cannot be eliminate with the help of the following table
“9.0 troubleshooting table”, the supplier or manufacturer should be consulted.
9.0 Troubleshooting Table
-
ATTENTION !
It is essential that the safety regulations are observed when identifying faults.
ATTENTION !
- read item 10.0 and 11.0 prior to dismantling and repair work!
- read item 6.0 before restarting the plant !
Fault
Possible cause
Corrective measures
No flow
Valve closed
Open valve (using actuator)
Flange covers not removed
Remove flange covers
Little flow
Valve not sufficiently open
Open valve (using actuator)
Dirt sieve clogged
Clean / replace sieve
Piping system clogged
Check piping system
Kvs value of valve unsuitable
Fit valve with higher Kvs value
Valve stem moves in jerks. Valve plug slightly seized owing to solid
dirt particles
Clean internals, smooth rough spots
Valve stem or plug cannot
be moved.
Seatring and plug clogged with dirt
Clean seatring and plug with suitable
solvent
Valve plug seized in seatring or guide
owing to deposits or dirt in medium
Replace plug and seatring
With straight trough version, the O-ring
in the seat ring groove was not
removed
Remove O-ring; refer to item 7.3.3
Valve stem leaking.
Stem seal leaking
Replace stem seal;
refer to item 7.1
Leakage too high when
valve is closed.
Sealing surfaces of plug eroded or
worn
Replace plug; refer to item 7.3.2.
Sealing edge of seatring damages or
worn
Replace seatring; refer to item 7.3.2
Seatring and/or plug dirty.
Clean internals of valve
Actuator not powerful enough
Install more powerful actuator,
Check service data
Valve stem „hammers“.
flow in the closing direction
increase actuator force