Operating and installation instructions

Str. thr. control valves - STEVI

®

440 / 441, 445 / 446

7.1.2 Stuffing box packing design
- The stuffing box packing (pos. 23) requires maintenance.
- If leaks develop, immediately tighten the screw joint (pos. 25) gradually until the packing

(pos. 23) stops leaking.

- The service life of stuffing box packings (pos. 23) can be increased by checking regularly

leakage.

- If leaks can no longer be stopped by tightening the screw joint (pos. 25), a new packing

ring (pos. 23) must be inserted into the gland.

Replacement of stuffing box packings:

- Remove actuator. (Refer to operating instructions for actuator!)
- Insert new packing ring as shown in Fig. 19 - Fig. 21.

Damaged stems must also be replaced (refer to item 7.2 for instructions) since a new ring
pack will soon start leaking again if the stem is damaged.

ATTENTION !
Refer to item 10.0 and 11.0
before dismantling the valve.

Fig. 19: Stuffing box packing

DN15-150

Fig. 20: Stuffing box packing

DN125v-150v / DN200-250

Fig. 21: Split packing ring

If a split packing ring is used, cut with a chamfer
as shown in Fig. 21.