beautypg.com

Maintenance, Venting system, Intake air screen – State SBL95 250NE A User Manual

Page 28: Temperature-pressure relief valve test, Anode rod inspection

background image

28

Venting system

examine the venting system every six months for obstructions

and/or deterioration of the vent piping. Check all vent system

connections for leakage and repair or reseal as necessary.
remove all soot or other obstructions from chimney which will

retard free draft.

intake air sCreen

The intake air screen is attached to the inlet end of the combustion

blower. Inspect the intake air screen every six months. The intake air

screen should be cleaned of any buildup of debris or foreign material.

temperature-pressure relief ValVe test

• Burn hazard.

• Hot water discharge.

• Keep clear of Temperature-

Pressure Relief Valve

discharge outlet.

It is recommended that the Temperature-Pressure relief Valve

should be checked to ensure that it is in operating condition

every 6 months.
When checking the Temperature-Pressure relief Valve operation,

make sure that (1) no one is in front of or around the outlet of the

Temperature-Pressure relief Valve discharge line, and (2) that

the water discharge will not cause any property damage, as the

water may be extremely hot. Use care when operating valve as

the valve may be hot.
To check the relief valve, lift the lever at the end of the valve

several times, see Figure 25. The valve should seat properly and

operate freely.
If after manually operating the valve, it fails to completely reset and

continues to release water, immediately close the cold water inlet

to the water heater and drain the water heater, see Draining and

Flushing on page 29. replace the Temperature-Pressure relief
Valve with a properly rated/sized new one, see Temperature-

Pressure relief Valve on pages 13-14 for instructions on

replacement.

figure 25.

If the Temperature-Pressure relief Valve on the water heater

weeps or discharges periodically, this may be due to thermal

expansion.
NOTe: excessive water pressure is the most common cause of

Temperature-Pressure relief Valve leakage. excessive water

system pressure is most often caused by "thermal expansion"

in a "closed system." See Closed Water Systems and Thermal

expansion on page 13. The Temperature-Pressure relief Valve

is not intended for the constant relief of thermal expansion.
Temperature-Pressure relief Valve leakage due to pressure build

up in a closed system that does not have a thermal expansion

tank installed is not covered under the limited warranty. Thermal

expansion tanks must be installed on all closed water systems.
DO NOT PlUG THe TeMPerATUre-PreSSUre relIeF

VAlVe OPeNING. THIS CAN CAUSe PrOPerTY DAMAGe,

SerIOUS INJUrY Or DeATH.

explosion hazard

Temperature-Pressure relief Valve

must comply with ANSI Z21.22-

CSA 4.4 and ASMe code.

Properly sized temperature-

pressure relief valve must be

installed in opening provided.

Can result in overheating and

excessive tank pressure.

Can cause serious injury or death.

anode rod inspeCtion

The anode rod is used to protect the tank from corrosion. Most

hot water tanks are equipped with an anode rod. The submerged

rod sacrifices itself to protect the tank. Instead of corroding tank,

water ions attack and eat away the anode rod. This does not affect

water’s taste or color. The rod must be maintained to keep tank

in operating condition.
Anode deterioration depends on water conductivity, not necessarily

water condition. A corroded or pitted anode rod indicates high

water conductivity and should be checked and/or replaced more

often than an anode rod that appears to be intact. replacement

of a depleted anode rod can extend the life of your water heater.

Inspection should be conducted by a qualified technician, and at

a minimum should be checked annually after the warranty period.
Artificially softened water is exceedingly corrosive because the

process substitutes sodium ions for magnesium and calcium ions.
The use of a water softener may decrease the life of the water

heater tank.
The anode rod should be inspected after a maximum of three

years and annually thereafter until the condition of the anode

rod dictates its replacement. Anode replacement is not covered

by warranty.
NOTe: Artificially softened water requires the anode rod to be

inspected annually.

maintenanCe

This manual is related to the following products: