beautypg.com

State SSX100 User Manual

Page 25

background image

25

VERtICAL tERMInAtIOn InstALLAtIOn

1. Determine the location for the termination(s).

nOtE: The standard vent and intake air terminations are of

different design, see Figure 18.

2. If installing only the vent (exhaust) piping in a Power Vent

configuration vertically through the roof; ensure that all

exterior vertical clearance requirements shown in Figure 19

and Figure 20 on page 26 are being maintained. These

clearances and those cited by local and national codes must

be maintained.
nOtE: on flat roof installations the vent termination must be

a minimum of 24 inches (60 cm) above any parapet, vertical

wall or structure within 10 feet (3 m) horizontally. See Figure

20 on page 26.

3. If installing both intake air and vent piping in a Direct Vent

configuration vertically through the roof; ensure that all

exterior vertical clearance requirements shown in Figure 19

and Figure 20 on page 26 are being maintained. These

clearances and those cited by local and national codes must

be maintained.
nOtE: on flat roof installations the intake air and the vent

terminations must be a minimum of 24 inches (60 cm) above

any parapet, vertical wall or structure within 10 feet (3 m)

horizontally. See Figure 20 on page 26.

4. If installing only vent piping in a Power Vent configuration

vertically through the roof the following instructions must be

followed:
The vent termination must be oriented facing downward as

shown in Figure 19 and Figure 20 on page 26.
The bottom edge of the vent termination must be a minimum

of 12 inches (30 cm), 18 inches (45 cm) in Canada, above

the average or expected snow level as shown in Figure 19

on page 26.

5. If installing both intake air and vent piping in a Direct Vent

configuration vertically through the roof the following

instructions must be followed:
The intake air and vent pipes must penetrate the same side

of the roof as shown in Figure 21 on page 26.
The intake air and vent terminations must be oriented facing

downward and in the same direction as shown in Figure 21

on page 26.

The intake air and vent terminations must have a minimum

separation of 24” (61 cm) measured on center line as shown

in Figure 21 on page 26. In colder climates this separation

should be increased to at least 48 inches (122 cm).
The bottom edge of the intake air and vent terminations

must be a minimum of 12 inches (30 cm), 18 inches (45 cm)

in Canada, above the average or expected snow level as

shown in Figure 19 and Figure 21 on page 26.

6. When the intake air and/or vent piping from multiple

water heaters will terminate in the same location the vent

terminations can be grouped together in close proximity 0

inches/touching. Intake air terminations can also be grouped

together in close proximity 0 inches/touching.
The distance between the closest vent and intake air

terminations must be a minimum of 24 inches (61 cm) as

shown in Figure 21 on page 26. In colder climates this

separation should be increased to at least 48 inches (122

cm).

7. Cut a 4 inch (10 cm) diameter hole for 3 inch pipe or 5 inch

(13 cm) diameter hole for 4 inch pipe where the pipe(s) will

pass through the roof.
nOtE: beware of concealed wiring and piping when cutting

through the roof.

8. Suspend the pipe(s) through center of hole using field

supplied metal strapping or equivalent support materials as

shown in Figure 19 on page 26.

9. Slide a roof boot or equivalent flashing over the pipe and

secure roof boot or equivalent flashing to roof and seal

around the flashing as shown in Figure 19, Figure 20 and

Figure 21 on page 26.

10. Install the factory supplied intake air and/or vent termination(s)

using field supplied pipe and one field supplied 90° elbow as

shown in Figure 19 on page 26. The short section of pipe

that connects between the field supplied 90° elbow and the

factory supplied termination must not be excessive in length.

The exposed portion of this pipe shall be no more than 2

inches (5 cm), see Figure 19 on page 26.

11. return to Power Vent Installation on page 23 or Direct Vent

Installation on page 23 to complete the installation of the intake

air and/or vent piping between the termination(s) and the

water heater.

STANDARD FACTORY SUPPLIED TERMINATIONS

INTAKE AIR TERMINATION

45° ELBOW WITH

DOME SHAPED DEBRIS

SCREEN

VENT TERMINATION

45° ELBOW WITH

RECESSED DEBRIS

SCREEN

figure 18

This manual is related to the following products: