beautypg.com

Water system piping, Piping installation – State SBV 65 10TS User Manual

Page 6

background image

6

Water System Piping

FIGURE 7

JACKET TOP WATER CONNECTION LOCATIONS

COLD INLET

ANODE

SOLAR IN (DOWN)*

SOLAR OUT (UP)*

119

GALLON

ONLY

HOT OUTLET

TEMPERATURE AND

PRESSURE RELIEF VALVE

*SEE FIGURE 8 FOR SIDE SOLAR CONNECTIONS (OPTIONAL). YOU MAY USE

EITHER THE TOP OR THE SIDE SOLAR CONNECTIONS.

Piping, fi ttings, and valves should be installed according to
the installation drawing (Figure 8). If the indoor installation
area is subject to freezing temperatures, the water piping
must be properly insulated.

IN A CLOSED SYSTEM

USE EITHER:

1. THERMAL EXPANSION TANK

2. PRESSURE RELIEF VALVE

PRESSURE REDUCING

VALVE WITH BYPASS

COLD WATER

INLET

COLD WATER

INLET VALVE

MIXED HOT

WATER

OUTLET

UNION

TEMPERATURE AND

PRESSURE RELIEF VALVE

DISCHARGE LINE

(DO NOT CAP OR PLUG)

DRAIN LINE

3/4 INCH ID

MINIMUM

DRAIN

SUITABLE DRAIN PAN

2-1/2 INCH DEPTH MAX.

1 INCH

MIN.

M A S S A C H U S E T T S :

INSTALL A VACUUM

RELIEF IN COLD
WATER

LINE PER

SECTION 19 MGL 142.

FIGURE 8

WATER PIPING INSTALLATION

MIXING

VALVE

SOLAR OUT (UP)*

SOLAR IN (DOWN)*

6 INCH MAXIMUM AIR GAP

BETWEEN THE END OF THE

DISCHARGE LINE AND DRAIN

SOLAR IN (From Collector)*

* YOU MAY USE EITHER THE TOP OR THE SIDE SOLAR CONNECTIONS.

SOLAR OUT (To Collector)*

The water supply pressure should not exceed 80 psi. If this
occurs, a pressure reducing valve with a bypass should be
installed in the cold water inlet line. This should be placed
on the supply to the entire house in order to maintain equal
hot and cold water pressures.

IMPORTANT:

Heat must not be applied to the water fittings on the heat-
er as they may contain nonmetallic parts. If solder con-
nections are used, solder the pipe to the adapter before
attaching the adapter to the hot and cold water fittings.

Always use a good grade of joint compound and be cer-
tain that all fittings are tight.

Piping Installation

1. Install the water piping and fittings as shown in

Figure 8. Connect the cold water supply (3/4” NPT) to
the fitting marked “Cold Water In”. Connect the hot water
supply (3/4” NPT) to the fitting marked “Hot Water Out”.

IMPORTANT: Some models may contain energy saving
heat traps to prevent the circulation of hot water within the
pipes. Do not remove these inserts.

2. The installation of unions in both the hot and cold water

supply lines are recommended for ease of removing the
solar storage tank water heater for service or replacement.

3. The manufacturer of this solar storage tank water heater

recommends installing a mixing valve or an anti-scald
device in the domestic hot water line as shown in Figure
9. These valves reduce the point-of-use temperature of
the hot water by mixing cold and hot water and are readily
available. Contact a licensed plumber or the local plumbing
authority. Install a spring check valve in the cold water inlet
to the mixing valve (See Figure 9). Connect the piping
that will carry the water from the solar storage tank to the
solar collectors, then to the fitting marked “SOLAR OUT.”
Connect the return line from the solar collectors to the
fitting marked “SOLAR IN.” You may use either the top
connections or the side connections (see Figure 8).

IMPORTANT: Cap or plug the solar connections that are
not used.

FIGURE 9

MIXING VALVE

TOP WATER CONNECTIONS

SOLAR IN (To Collector)

COLD

WATER

INLET

MIXING

VALVE TO

FIXTURES

MIXING VALVE

(SET TO 120° F)

SOLAR OUT (To Collector)

SPRING

CHECK VALVE

MIXED

HOT

WATER

OUTLET

4. Recirculation return lines should be connected to an

auxiliary solar storage tank water heater (see Figure
10, Page 7). DO NOT connect recirculation lines to
the solar storage tank. Recirculation pumps should be
controlled by a timer which will stop circulation at night
or any time hot water is not being used.

5. If components in the solar control system have

maximum working pressures that are lower than the
maximum water supply pressure, a pressure reducing
valve with an integral strainer and by-pass should
be installed in a cold water supply line. The pressure